4-10 Compaq 3000 Series UPS Operation and Reference Guide
Table
Operating Ranges (VAC) – North America and Japanese Models
Nominal Level |
| Normal Range |
| Extended Range |
100 |
| 80 to 120 |
| Not applicable for R3000j |
|
|
|
|
|
110 |
| 88 to 132 |
| 72 to 132 |
|
|
|
|
|
120 |
| 96 to 144 |
| 78 to 144 |
|
|
|
|
|
127 |
| 102 to 152 |
| 83 to 155 |
|
|
|
|
|
Table
Operating Ranges (VAC) – All High Voltage Models
Nominal Level |
| Normal Range |
| Extended Range |
208 |
| 166 to 250 |
| Not applicable for |
|
|
|
| |
|
|
|
|
|
220 |
| 176 to 264 |
| 143 to 264 |
|
|
|
|
|
230 |
| 184 to 276 |
| 150 to 276 |
|
|
|
|
|
240 |
| 192 to 288 |
| 156 to 288 |
|
|
|
|
|
3.For nominal voltage level setting, select configuration parameters 1, 2, 3, or 10 (see Table
4.Access parameter 4 to switch from normal to extended range (see Table