Compaq 3000 Series manual Front Panel Indicators, Front Panel LEDs Standby and Operate Modes

Models: 3000 Series

1 96
Download 96 pages 21.07 Kb
Page 38
Image 38

Operation 3-5

Front Panel Indicators

The front panel LED display colors indicate the UPS status:

Green LEDs indicate normal conditions

Red LEDs provide warning of existing or potential problems

LEDs are referred to as LED 1 through 16, as described in this documentation.

When the UPS is in Configure mode, the LEDs do not operate as they do in the Standby and Operate modes (see Chapter 4, “Configuration”).

Front Panel LEDs in the

Standby and Operate Modes

Each LED (and the condition it indicates in the Operate and Standby modes) is described in the following tables:

AC Input (LEDs 1-4)

 

 

 

 

Table 3-1

 

 

 

 

AC Input LEDs

 

 

 

 

 

LED

 

Color

 

Meaning

 

 

 

 

 

1

 

Red

 

The utility voltage is higher than the voltage range for which the

 

 

 

 

UPS has been configured. The UPS is supplying battery power.

 

 

 

 

The audio alarm will sound.

 

 

 

 

 

 

 

Flashing Red

 

Utility voltage has returned to the voltage range for which the UPS

 

 

 

 

has been configured. The UPS is supplying utility power. The

 

 

 

 

audio alarm should be reset.

 

 

 

 

 

2

 

Green

 

Utility voltage is within the voltage range for which the UPS has

 

 

 

 

been configured.

 

 

 

 

 

3

 

Green

 

Utility voltage is lower than the current UPS configuration expects.

 

 

 

 

The UPS is compensating and providing power to the loads

 

 

 

 

without the use of batteries.

 

 

 

 

 

4

 

Red

 

The utility voltage is lower than the voltage range for which the

 

 

 

 

UPS has been configured. The UPS is supplying battery power.

 

 

 

 

The audio alarm will sound.

 

 

 

 

 

 

 

Flashing Red

 

Utility voltage has returned to the voltage range for which the UPS

 

 

 

 

has been configured. The UPS is supplying utility power. The

 

 

 

 

audio alarm should be reset.

 

 

 

 

 