Compaq 3000 Series manual Preparing the UPS, Removing the Battery Pack

Models: 3000 Series

1 96
Download 96 pages 21.07 Kb
Page 61
Image 61

Battery Maintenance 5-5

Step 1: Preparing the UPS

To replace batteries with the UPS Off

1.Shut down all load devices.

2.Press the STANDBY button to take the UPS out of Operate mode. The ON LED extinguishes, and power to the load receptacles ceases.

3.Disconnect the UPS from utility power.

4.Wait at least 60 seconds, while the UPS internal circuitry discharges.

To replace batteries with the UPS in

Operate mode (hot-swapping)

Batteries may be replaced (hot-swapped) without powering off the UPS if both of the following conditions are met:

The UPS is not charging the batteries (Battery Charge LEDs 6, 7, and 8 are all green, indicating that the batteries are fully charged).

NOTE: Older batteries may be fully charged but still incapable of providing adequate backup for devices. Therefore, the battery charge LEDs can indicate the batteries are fully charged, while the UPS diagnostics have determined that the batteries need to be replaced.

The UPS is not supplying battery power to devices (AC Input LEDs 1 and 4 are green, indicating that the UPS is supplying utility power).

Step 2: Removing the Battery Pack

Follow this procedure to remove the battery pack:

1.To obtain access to the battery pack, remove the four screws holding the faceplate; detach the faceplate sufficiently to disconnect the LED display cable.

Page 61
Image 61
Compaq 3000 Series manual Preparing the UPS, Removing the Battery Pack, To replace batteries with the UPS Off