Compaq R6000 Series manual Set Voltage, Set Site Fault, Set Sleep Mode, Configuration

Models: R6000 Series

1 123
Download 123 pages 126 b
Page 78
Image 78
Set Voltage

Configuration 4-21

Set Voltage

The Compaq R6000 UPS must be placed in manual Bypass using the switch at the rear of the unit, and placed into Standby mode (see Chapter 3, “Operation”) to set the voltage.

The voltage that is set will appear with an “*”. Using the Center button, scroll through the voltages and choose using the Enter button. The choices are:

200 V

208 V

220 V

230 V

240 V

208/230 V Auto Sensing

230 V Extended

Set Voltage

208V

Set Site Fault

The two values are “Disable” or “Enable.” Use the Center button to scroll and the Enter button to select. An asterisk, “*” marks the selected value.

Set Site Fault

Enable

Set Sleep Mode

When Sleep Mode is enabled, if the UPS is supplying battery power and the load on the UPS is less than 8%, the UPS switches to Sleep mode (the UPS shuts itself off). Use the Center and Enter buttons to “Enable” or “Disable” this feature. An “*” will mark the selected value.

Set Sleep Mode

Enable

Page 78
Image 78
Compaq R6000 Series manual Set Voltage, Set Site Fault, Set Sleep Mode, Configuration