6-6 Compaq R6000 UPS Series Operation and Reference Guide
Caution Audible Alarm
Table 
Caution Audible Alarm
| Audible Alarm Group | Audible Alarm Sound | Cause(s) | Action | 
| Caution | Beeps every five | On battery | Prepare for UPS shutdown. | 
| 
 | seconds | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | Load is greater than | Check manual Bypass | 
| 
 | 
 | 105%, and the manual | switch on back of UPS. Turn | 
| 
 | 
 | Bypass switch is turned | to Normal position. Reduce | 
| 
 | 
 | to Bypass position. | load. | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | Ambient over- | Check air intake is not | 
| 
 | 
 | temperature | blocked and ambient room | 
| 
 | 
 | 
 | temperature is correct. If the | 
| 
 | 
 | 
 | problem still exists, contact | 
| 
 | 
 | 
 | an authorized service | 
| 
 | 
 | 
 | provider. | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | Button is still being held | Let go of button. Make sure | 
| 
 | 
 | after action is | the button travels freely, or | 
| 
 | 
 | completed. | is not lodged. | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | The UPS performs a | Turn off the UPS and call an | 
| 
 | 
 | authorized service provider. | |
| 
 | 
 | memory location error. | 
 | 
| 
 | 
 | 
 | 
 | 
| 
 | 
 | Use the Front Panel controls | |
| 
 | 
 | if the  | and LCD display to examine | 
| 
 | 
 | enabled.) | information on the warning. | 
| 
 | 
 | 
 | If necessary, contact a | 
| 
 | 
 | 
 | licensed electrician to check | 
| 
 | 
 | 
 | input wiring, or contact an | 
| 
 | 
 | 
 | authorized service provider. | 
| 
 | 
 | 
 | 
 | 
A self-test  fails, indicated on the LCD display
Shut off Mains, wait until UPS shuts down, then turn breaker back ON and test again. If 
continued