6-2Compaq R6000 UPS Series Operation and Reference Guide

Responding to Audible Alarms

Acknowledgement Audible Alarm

Table 6-1

Acknowledgement Audible Alarm

Audible Alarm Group

Audible Alarm Sound

Cause(s)

Action

Acknowledgement

Single short beep.

The ON or TEST button

No action needed.

 

 

was pressed.

 

 

 

The self or battery test

No action needed.

 

 

completes successfully.

 

 

 

 

 

Shutdown Imminent Audible Alarm

Table 6-2

Shutdown Imminent Audible Alarm

Audible Alarm Group

Audible Alarm Sound

Cause(s)

Action

Shutdown Imminent

Single long beep.

Heat sink

UPS will shut down in 3

 

 

over temperature

seconds. Contact an

 

 

while on battery.

authorized service provider.

 

 

 

 

 

 

Remote Emergency

Check position of REPO

 

 

Power Off.

switch. Open the REPO

 

 

(Switch “closed,” or

switch.

 

 

input low.)

 

 

 

 

 

Page 91
Image 91
Compaq R6000 Series manual Responding to Audible Alarms, Audible Alarm Group, Causes Action Shutdown Imminent