Identifying Controller Faults
This chapter describes how to troubleshoot your controller. Topics include:
•identifying controller faults
•contacting Rockwell Automation for assistance
While a program is executing, a fault may occur within the operating system or your program. When a fault occurs, you have various options to determine what the fault is and how to correct it. This section describes how to clear faults and provides a list of possible advisory messages with recommended corrective actions.
Automatically Clearing Faults
You can automatically clear a fault by cycling power to the controller when the Fault Override at
You can also configure the controller to clear faults and go to RUN every time the controller is power cycled. This is a feature that OEMs can build into their equipment to allow end users to reset the controller. If the controller faults, it can be reset by simply cycling power to the machine. To accomplish this, set the following bits in the status file:
•S2:1/8 - Fault Override at
•S2:1/12 - Mode Behavior
If the fault condition still exists after cycling power, the controller
NOTE | You can declare your own | |
by writing your own unique value to S:6 and then setting | ||
| ||
| ||
| bit S:1/13 to prevent reusing system defined codes. The | |
| recommended values for | |
| FF0F. |