Fault Messages and Error Codes

D-5

 

 

Error

Advisory Message

Description

Fault

Recommended Action

Code

 

 

Classification

 

(Hex)

 

 

 

 

 

 

 

 

 

0028

INVALID OR

A fault routine number was

Non-User

Either clear the fault routine file number

 

NONEXISTENT USER

entered in the status file, number

 

(S:29) in the status file, or

 

FAULT ROUTINE

(S:29), but either the fault routine

 

create a fault routine for the file number

 

VALUE

was not physically created, or

 

reference in the status file (S:29). The file

 

 

the fault routine number was less

 

number must be greater than 2 and less

 

 

than 3 or greater than 255.

 

than 256.

 

 

 

 

 

0029

INSTRUCTION

An indirect address reference in the

Recoverable

Correct the program to ensure that there are

 

INDIRECTION

ladder program is outside of the

 

no indirect references outside data file space.

 

OUTSIDE OF DATA

entire data file space.

 

Re-compile, reload the program and enter the

 

SPACE

 

 

Run mode.

 

 

 

 

 

002E

EII ERROR

An error occurred in the EII

Recoverable

See the Error Code in the EII Function File for

 

 

configuration.

 

the specific error.

 

 

 

 

 

0030

SUBROUTINE

The JSR instruction nesting level

Non-User

Correct the user program to reduce the

 

NESTING EXCEEDS

exceeded the controller memory

 

nesting levels used and to meet the

 

LIMIT

space.

 

restrictions for the JSR instruction. Then

 

 

 

 

reload the program and Run.

 

 

 

 

 

0031

UNSUPPORTED

The program contains an

Non-User

Modify the program so that all instructions

 

INSTRUCTION

instruction(s) that is not supported

 

are supported by the controller.

 

DETECTED

by the controller.

 

Re-compile and reload the program and

 

 

 

 

enter the Run mode.

 

 

 

 

 

0032

SQO/SQC/SQL

A sequencer instruction length/

Recoverable

Correct the program to ensure that the

 

OUTSIDE OF DATA

position parameter references

 

length and position parameters do not

 

FILE SPACE

outside of the entire data file space.

 

point outside data file space.

 

 

 

 

Re-compile, reload the program and enter

 

 

 

 

the Run mode.

 

 

 

 

 

0033

BSL/BSR/FFL/FFU/LFL/

The length/position parameter of a

Recoverable

Correct the program to ensure that the

 

LFU CROSSED DATA

BSL, BSR, FFL, FFU, LFL, or LFU

 

length and position parameters do not

 

FILE SPACE

instruction references outside of the

 

point outside of the data space.

 

 

entire data file space.

 

Re-compile, reload the program and enter

 

 

 

 

the Run mode.

 

 

 

 

 

0034

NEGATIVE VALUE IN

A negative value was loaded to a

Recoverable

If the program is moving values to the

 

TIMER PRESET OR

timer preset or accumulator.

 

accumulated or preset word of a timer,

 

ACCUMULATOR

 

 

make certain these values are not

 

 

 

 

negative.

 

 

 

 

Reload the program and enter the Run

 

 

 

 

mode.

 

 

 

 

 

0035

ILLEGAL

The program contains a Temporary

Non-Recoverable

Correct the program.

 

INSTRUCTION IN

End (TND), Refresh (REF), or Service

 

Re-compile, reload the program and enter

 

INTERRUPT FILE

Communication instruction in an

 

the Run mode.

 

 

interrupt subroutine (STI, EII, HSC) or

 

 

 

 

user fault routine.

 

 

 

 

 

 

 

0036

INVALID PID

An invalid value is being used for a

Recoverable

Process Control Instruction for

 

PARAMETER

PID instruction parameter.

 

more information about the PID instruction.

 

 

 

 

 

0037

HSC ERROR

An error occurred in the HSC

Recoverable

See the Error Code in the HSC Function File

 

 

configuration.

 

for the specific error.

 

 

 

 

 

003B

PTO ERROR

An error occurred in the PTO

Recoverable or

See the Error Code in the PTO Function File for

 

 

instruction configuration.

Non-User

the specific error.

 

 

 

 

 

003C

PWM ERROR

An error occurred in the PWM

Recoverable or

See the Error Code in the PWM Function File

 

 

instruction configuration.

Non-User

for the specific error.

 

 

 

 

 

Basic 32 Loader Control

UGC007/0702