D-6Fault Messages and Error Codes

Error

Advisory Message

Description

Fault

Recommended Action

Code

 

 

Classification

 

 

(Hex)

 

 

 

 

 

 

 

 

 

 

003D

INVALID SEQUENCER

A sequencer instruction (SQO, SQC,

Recoverable

Correct the user program, then re-compile,

 

LENGTH/POSITION

SQL) length/position parameter is

 

reload the program and enter the Run mode.

 

 

greater than 255.

 

 

 

 

 

 

 

 

003E

INVALID BIT SHIFT OR

A BSR or BSL instruction length

Recoverable

Correct the user program or allocate more

 

LIFO/FIFO

parameter is greater than 2048 or an

 

data file space using the memory map, then

 

PARAMETER

FFU, FFL, LFU, LFL instruction length

 

reload and Run.

 

 

parameter is greater than 128 (word

 

 

 

 

 

file) or greater than 64 (double word

 

 

 

 

 

file)

 

 

 

 

 

 

 

 

 

003F

COP/FLL OUTSIDE OF

A COP or FLL instruction length

Recoverable

Correct the program to ensure that the

 

DATA FILE SPACE

parameter references outside of the

 

 

length and parameter do not point outside

 

 

entire data space.

 

 

of the data file space.

 

 

 

 

Re-compile, reload the program and enter

 

 

 

 

 

the Run mode.

 

 

 

 

 

 

0050

CONTROLLER TYPE

A particular controller type was

Non-User

Connect to the hardware that is specified

 

MISMATCH

selected in the user program

 

 

in the user program, or

 

 

configuration, but did not match the

 

Reconfigure the program to match the

 

 

actual controller type.

 

 

attached hardware.

 

 

 

 

 

 

0051

BASE TYPE

A particular hardware type (AWA,

Non-User

Connect to the hardware that is specified

 

MISMATCH

BWA, BXB) was selected in the user

 

 

in the user program, or

 

 

program configuration, but did no

 

Reconfigure the program to match the

 

 

match the actual base.

 

 

attached hardware.

 

 

 

 

 

 

0052

MINIMUM SERIES

The hardware minimum series

Non-User

Connect to the hardware that is specified

 

ERROR

selected in the user program

 

 

in the user program, or

 

 

configuration was greater than the

 

Reconfigure the program to match the

 

 

series on the actual hardware.

 

 

attached hardware.

 

 

 

 

 

 

0070

EXPANSION I/O

The required expansion I/O

Non-Recoverable

Check the expansion I/O terminator on the

 

TERMINATOR

terminator was removed.

 

 

last

 

REMOVED

 

 

 

I/O module.

 

(MicroLogix 1500 only)

 

 

Cycle power.

 

 

 

 

 

 

xx71(1)

EXPANSION I/O

The controller cannot communicate

Non-Recoverable

Check connections.

 

HARDWARE ERROR

with an expansion I/O module.

 

Check for a noise problem and be sure

 

 

 

 

 

proper grounding practices are used.

 

 

 

 

Replace the module.

 

 

 

 

Cycle power.

 

 

 

 

 

 

xx79(1)

EXPANSION I/O

An expansion I/O module generated

Non-Recoverable

Refer to the I/O Module Status (IOS) file.

 

MODULE ERROR

an error.

 

Consult the documentation for your

 

 

 

 

 

specific I/O module to determine possible

 

 

 

 

 

causes of a module error.

 

 

 

 

 

 

0080

EXPANSION I/O

The required expansion I/O

Non-User

Check expansion I/O terminator on last I/O

 

TERMINATOR

terminator was removed.

 

 

module.

 

REMOVED

 

 

Cycle power.

 

(MicroLogix 1500 only)

 

 

 

 

 

 

 

 

 

 

xx81(1)

EXPANSION I/O

The controller cannot communicate

Non-User

Check connections.

 

HARDWARE ERROR

with an expansion I/O module.

 

Check for a noise problem and be sure

 

 

 

 

 

proper grounding practices are used.

 

 

 

 

Replace the module.

 

 

 

 

Cycle power.

 

 

 

 

 

 

Basic 32 Loader Control UGC007/0702