Cornelius Cold Beverage Dispenser manual Shurflow Installation, Start-Up Procedure

Models: Cold Beverage Dispenser

1 48
Download 48 pages 2.76 Kb
Page 20
Image 20
SHURFLOW INSTALLATION

IntelliCarb Training Manual

SHURFLOW INSTALLATION

As indicated on the pump, the outlet port is to be mounted up.

Pumps are to be mounted at the same level or higher than the B-I-B. The best choice is to have the pump above the B-I-B.

INLET tubing from the B-I-B to the pump use; 3/8" I.D. [10mm] minimum, heavy wall (1/8" [3mm]) clear, NSF listed vacuum tubing. Inlet tubing should not have excessive length. Tub- ing that is allowed to drape down can trap air in the B-I-B creating a potential for pump "sold- out" problems. The maximum vertical distance from the bottom of the B-I-B to the pump must not exceed 5 ft [1.5 M ]. Maximum inlet tubing length is 10 ft. [3 M ].

If plumbing multiple B-I-B’s to a pump, B-I-B's should be "Teed" side-by-sidehorizontally, rather than one on top of the other (vertically).

OUTLET tubing from the pump to the dispenser should be high pressure rated and NSF listed. Consult "Pumping Capability" (see page 2) for appropiate tubing I.D.

Always cut CO2 and outlet tubing at least 2 ft. [.6 M] longer to provide a "service loop" so the B-I-B rack can be moved for cleaning or service.

Use new (clean), 1/4" I.D. [6 mm], flexible, high pressure, braided tubing from the CO2 / air regulator to the pump.

NEVER connect a transfer tank "system" in series with a B-I-B system. Syrup contaminants in old components may work their way through the air supply causing premature failure of the gas pump. Gas used to operate pumps MUST be clean and contain no contaminants (syrup, oil, rust, water, etc). Air compressors may be used with proper particle filters and moisture separators. Air storage tanks should be drained regularly. Pumps subjected to contaminated air are not covered by warranty.

High concentrations of CO2 can be fatal as it will displace the air from non-ventilated areas. Pumps operated by CO2 must be in ventilated areas.

If placed in a confined area (basement, closet, cooler box, etc.), exhaust fans capable of changing the room air on a continuous basis should be used.

All tubing connections must be secured with stainless steel, stepless Oetiker ® clamps.

Cable-tie all tubing securely to prevent kinks or sags that inhibit performance or cause damage to the pump fittings.

START-UP PROCEDURE

1.Confirm that all tubing connections are properly clamped, fittings are tight, and tubing is not kinked. Install bag connector to the B-I-B.

2.Adjust gas regulator to about 20 psi. [1.4 bar] allowing the pump to stroke slowly.

3.Operate the valve until all air trapped within the tubing has been purged.

4.Once the air has been purged, adjust the CO2 regulator to the pressure necessary to main- tain the desired brix. The most efficient gas usage occurs at 40 psi. [2.8 bar]. MAXIMUM static gas pressure to the pump is 85 psi. [5.8 bar], minimum 20 psi. [1.4 bar].

Flowrates that result in a stroke-rate of more than two strokes per second will decrease pump life. (Consult factory) Pump failure due to "overrunning" is not covered by the limited warranty.

To prevent air from entering the system always leave the bag connector attached to the empty B-I-B until a new B-I-B can be installed. Air entered into the system, via air in the bags or vacuum leaks, may cause brix fluctuation, foaming, spitting, non-operation of the vacuum sold- out or pump "run-on" with the valve closed. Symptoms of this kind can lead to a misdiagnosis of the

pump.

Publication Number: TP01071

- 16 -

© 2004, IMI Cornelius Inc.

Page 20
Image 20
Cornelius Cold Beverage Dispenser manual Shurflow Installation, Start-Up Procedure