![SHURFLOW INSTALLATION](/images/new-backgrounds/73318/7331839x1.webp)
IntelliCarb Training Manual
SHURFLOW INSTALLATION
•As indicated on the pump, the outlet port is to be mounted up.
•Pumps are to be mounted at the same level or higher than the
•INLET tubing from the
•If plumbing multiple
•OUTLET tubing from the pump to the dispenser should be high pressure rated and NSF listed. Consult "Pumping Capability" (see page 2) for appropiate tubing I.D.
•Always cut CO2 and outlet tubing at least 2 ft. [.6 M] longer to provide a "service loop" so the
•Use new (clean), 1/4" I.D. [6 mm], flexible, high pressure, braided tubing from the CO2 / air regulator to the pump.
NEVER connect a transfer tank "system" in series with a
High concentrations of CO2 can be fatal as it will displace the air from
If placed in a confined area (basement, closet, cooler box, etc.), exhaust fans capable of changing the room air on a continuous basis should be used.
•All tubing connections must be secured with stainless steel, stepless Oetiker ® clamps.
•
START-UP PROCEDURE
1.Confirm that all tubing connections are properly clamped, fittings are tight, and tubing is not kinked. Install bag connector to the
2.Adjust gas regulator to about 20 psi. [1.4 bar] allowing the pump to stroke slowly.
3.Operate the valve until all air trapped within the tubing has been purged.
4.Once the air has been purged, adjust the CO2 regulator to the pressure necessary to main- tain the desired brix. The most efficient gas usage occurs at 40 psi. [2.8 bar]. MAXIMUM static gas pressure to the pump is 85 psi. [5.8 bar], minimum 20 psi. [1.4 bar].
Flowrates that result in a
To prevent air from entering the system always leave the bag connector attached to the empty
pump.
Publication Number: TP01071 | - 16 - | © 2004, IMI Cornelius Inc. |