Environmental

 

Six consecutively executed shock pulses in the positive and negative x, y, and

 

z axes (one pulse on each side of the system) of 32 G faired square wave

 

pulse with velocity change at 270 inches/second (686 centimeters/second).

Maximum Altitude

 

Operating

3048 m (10,000

Storage

12,000 m (39,370 ft).

Operating Altitude De-rating

≤ 35 °C (95 °F)

Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m

 

(3,117 ft).

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.

Air Filtration

Conductive Dust

Corrosive Dust

Gaseous Contamination

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

NOTE: Applies to data center and non-data center environments.

Air must be free of conductive dust, zinc whiskers, or other conductive particles.

NOTE: Applies to data center and non-data center environments.

Air must be free of corrosive dust.

Residual dust present in the air must have a deliquescent point less than 60% relative humidity.

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Copper Coupon

<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.

Corrosion Rate

 

Silver Coupon

<200 Å/month as defined by AHSRAE TC9.9.

Corrosion Rate

 

80

Page 80
Image 80
Dell R220 owner manual 300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985