Emerson ITR Condensate Pump, Remote Temperature/ Humidity Sensors, Disconnect Switch-Locking Type

Models: ITR

1 74
Download 74 pages 51.84 Kb
Page 16
Image 16

Standard Features—All Systems

4.6.1

Condensate Pump

 

 

 

The condensate pump, mounted in the bottom of most units, is

 

used for unit drain water only. The condensate pump is complete

 

with sump, motor and pump assembly and automatic control.

 

The standard model has single float. A dual-float condensate

 

pump, which includes connections to unit, common alarm, unit

 

shutdown and one customer N/O contact is also available.

 

Table 1

Condensate pump capacity

 

 

 

 

 

 

 

 

 

Capacity

Head Pressure

 

 

Voltage

Hz

GPH (l/s)

ft. (kPa)

 

 

200/230

50

50 (189)

10 (30)

 

 

 

 

 

 

 

 

208/230

60

50 (189)

17 (51)

 

 

 

 

 

 

 

 

380/415

50

200 (757)

26 (78)

 

 

 

 

 

 

 

 

460

60

200 (757)

43 (128)

 

 

 

 

 

 

 

4.6.2 Remote Temperature/ Humidity Sensors

 

The remote temperature/ humidity sensors permit monitoring room conditions from an external

 

source. They are encased in an attractive case and are provided with a plug compatible shielded cable

 

in virtually any length.

 

 

4.6.3

Disconnect Switch—Locking Type

 

The locking disconnect switch, mounted in the electrical panel, is con-

 

nected to the safety lock dead front panel of the system and is inter-

 

locked mechanically. In this way the panel can’t be opened until the

switch is in the off position. And it complies with local codes as well as those of the NEC.

Disconnect Switch

(Locking)

8

Page 16
Image 16
Emerson ITR manual Condensate Pump, Remote Temperature/ Humidity Sensors, Disconnect Switch-Locking Type