System Data

13.0SYSTEM DATA

Table 2

Liebert Challenger ITR air-cooled data—60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Split Systems

 

System Type

 

 

 

w/Outdoor Prop-Fan

w/Indoor Centrifugal

 

BR = Horizontal Flow

Self-Contained

Condensing Unit

Condensing Unit

Indoor Unit

BR 067A

BR 060E

 

BR 060E

 

Net Capacity Data

BTU/H

 

kW

BTU/H

 

kW

BTU/H

 

kW

100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH

 

 

 

 

 

 

 

 

 

 

Total

78,100

 

22.9

76,200

 

22.3

73,200

 

21.4

 

Sensible

78,100

 

22.9

76,200

 

22.3

73,200

 

21.4

Non Standard Flow Rates

2400 CFM

2300 CFM

 

2100 CFM

 

95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH

 

 

 

 

 

 

 

 

 

 

Total

77,500

 

22.7

75,800

 

22.2

73,000

 

21.4

 

Sensible

77,500

 

22.7

75,800

 

22.2

73,000

 

21.4

 

Non Standard Flow Rates

 

 

 

2700 CFM

 

2500 CFM

 

90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH

 

 

 

 

 

 

 

 

 

 

Total

73,600

 

21.6

72,400

 

21.2

70,600

 

20.7

 

Sensible

73,600

 

21.6

72,400

 

21.2

70,600

 

20.7

85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH

 

 

 

 

 

 

 

 

 

 

Total

69,700

 

20.4

68,400

 

20.0

66,800

 

19.6

 

Sensible

69,700

 

20.4

68,400

 

20.0

66,800

 

19.6

80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH

 

 

 

 

 

 

 

 

 

 

Total

66,000

 

19.3

64,400

 

18.9

63,100

 

18.5

 

Sensible

66,000

 

19.3

64,400

 

18.9

63,100

 

18.5

80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH

 

 

 

 

 

 

 

 

 

 

Total

66,900

 

19.6

65,300

 

19.1

63,800

 

18.7

 

Sensible

54,600

 

16.0

54,000

 

15.8

53,400

 

15.6

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH

 

 

 

 

 

 

 

 

 

 

Total

62,700

 

18.4

60,800

 

17.8

59,600

 

17.5

 

Sensible

53,000

 

15.5

52,300

 

15.3

51,800

 

15.2

75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH

 

 

 

 

 

 

 

 

 

 

Total

61,200

 

17.9

60,700

 

17.8

59,600

 

17.5

 

Sensible

57,000

 

16.7

60,700

 

17.8

59,600

 

17.5

72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH

 

 

 

 

 

 

 

 

 

 

Total

60,200

 

17.6

58,200

 

17.1

57,200

 

16.8

 

Sensible

52,000

 

15.2

51,200

 

15.0

50,700

 

14.9

72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH

 

 

 

 

 

 

 

 

 

 

Total

58,900

 

17.3

58,400

 

17.1

57,500

 

16.8

 

Sensible

55,800

 

16.3

58,400

 

17.1

57,500

 

16.8

Fan Data (Blower A12x9AT)**

 

 

 

 

 

 

 

 

 

 

Standard Air, CFM (CMH)

2800 (4760)

2800 (4760)

 

2800 (4760)

 

 

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

1-1/2 (1.1)

 

1-1/2 (1.1)

 

 

Opt Fan Motor, hp (kW)

2 (1.5)

2 (1.5)

 

2 (1.5)

 

 

Ext Static, in. WG (Pa)

.3

(75)

.3 (75)

 

.3 (75)

 

Evaporator Coil (V-FRAME, at standard conditions)

 

 

 

 

 

 

 

 

 

 

Face Area, ft.2 (m2)

6.67 (.62)

6.67 (.62)

 

6.67 (.62)

 

 

Rows

 

4

 

4

 

 

4

 

 

 

Face Velocity - FPM (m/s)

405 (2.1)

405 (2.1)

 

405 (2.1)

 

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard

 

 

 

 

 

 

 

Capacity, inc. motor heat, BTU/H (element kW)

56,200 (15)

56,200 (15)

 

56,200 (15)

 

Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)

 

 

Capacity, inc. motor heat, BTU/H (kW)

88,700 (26.0)

88,700 (26.0)

88,700 (26.0)

 

Flow Rate - GPM (l/s)

5.0 (.32)

5.0 (.32)

 

5.0 (.32)

 

 

Pressure drop - ft. (kPa)

16.9 (50.4)

16.9 (50.4)

 

16.9 (50.4)

 

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

24