System Data

Table 6

Liebert Challenger ITR water cooled data, 60 Hz

 

 

 

 

 

 

 

 

 

 

 

System Type

Self-Contained

 

Split Systems

 

 

BR = Horizontal Flow

 

 

Indoor Unit

BR 071WG

 

BR 060E

 

 

 

 

 

 

 

Net Capacity Data

BTU/H

 

kW

BTU/H

 

kW

100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH

 

 

 

 

 

 

 

Total

82,900

 

24.3

79,000

 

23.1

 

 

 

 

 

 

 

 

 

Sensible

82,900

 

24.3

79,000

 

23.1

 

Non-Standard Flow Rates

2600 CFM

 

2400 CFM

 

95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

80,400

 

23.6

78,400

 

23.0

 

Sensible

80,400

 

23.6

78,400

 

23.0

 

 

 

 

 

 

 

90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH

 

 

 

 

 

 

 

Total

76,200

 

22.3

74,400

 

21.8

 

Sensible

76,200

 

22.3

74,400

 

21.8

 

 

 

 

 

 

 

85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH

 

 

 

 

 

 

 

Total

72,300

 

21.2

70,300

 

20.6

 

 

 

 

 

 

 

 

 

Sensible

72,300

 

21.2

70,300

 

20.6

80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH

 

 

 

 

 

 

 

Total

68,400

 

20.0

66,500

 

19.5

 

 

 

 

 

 

 

 

 

Sensible

68,400

 

20.0

66,500

 

19.5

80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

69,900

 

20.5

67,600

 

19.8

 

Sensible

55,700

 

16.3

54,900

 

16.1

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

65,200

 

19.1

63,100

 

18.5

 

Sensible

54,000

 

15.8

53,200

 

15.6

 

 

 

 

 

 

 

75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH

 

 

 

 

 

 

 

Total

63,600

 

18.6

61,500

 

18.0

 

Sensible

58,000

 

17.0

57,100

 

16.7

 

 

 

 

 

 

 

72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH

 

 

 

 

 

 

 

Total

62,500

 

18.3

60,500

 

17.7

 

 

 

 

 

 

 

 

 

Sensible

53,000

 

15.5

52,100

 

15.3

72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH

 

 

 

 

 

 

 

Total

61,100

 

17.9

59,200

 

17.3

 

 

 

 

 

 

 

 

 

Sensible

56,700

 

16.6

55,900

 

16.4

Fan Data (Blower A12x9AT)**

 

 

 

 

 

 

 

Standard Air, CFM (CMH)

2800 (4760)

 

2800 (4760)

 

 

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

 

1-1/2 (1.1)

 

 

Opt Fan Motor, hp (kW)

2 (1.5)

 

 

2 (1.5)

 

 

 

 

 

 

 

 

 

 

 

Ext Static, in. WG (Pa)

.3 (75)

 

 

.3 (75)

 

 

Evaporator Coil (V-Frame, at standard conditions)

 

 

 

 

 

 

 

Face Area, ft.2 (m2)

6.67 (.62)

 

6.67 (.62)

 

 

Rows

4

 

 

4

 

 

 

Face Velocity, FPM (m/s)

405 (2.1)

 

405 (2.1)

 

 

 

 

 

 

 

 

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard

 

 

 

 

 

Capacity, inc. motor heat, BTU/H (element kW)

56,200 (15)

 

56,200 (15)

 

 

 

 

 

 

 

Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)

 

 

Capacity, inc. motor heat, BTU/H (kW)

88,700 (26.0)

 

88,700 (26.0)

 

 

Flow Rate, GPM (l/s)

5.0 (.32)

 

5.0 (.32)

 

 

 

 

 

 

 

 

Pressure drop, ft. (kPa)

16.9 (50.4)

 

16.9 (50.4)

 

Hot Gas Reheat - Optional (Includes standard air volume and optional fan motor)

 

 

 

 

 

Capacity, inc. motor heat, BTU/H (kW)

54,900 (16.1)

 

54,900 (16.1)

 

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

28