Emerson ITR manual Fan speed control condensers, Liebert Lee-Temp condensers, Glycol DS0174

Models: ITR

1 74
Download 74 pages 51.84 Kb
Page 55
Image 55

Electrical Data

Table 23 Fan speed control condensers *

95°F (35°C) Ambient, 1 Phase - 60 Hz

CSF104

Voltage

208/230

460

575

 

 

 

 

FLA

4.8

2.5

1.9

WSA

6.0

3.1

2.4

 

 

 

 

OPD

15.0

15.0

15.0

 

 

 

 

* Contact factory for 380-3-60 data.

Table 24 Liebert Lee-Temp condensers *

95°F (35°C) Ambient, 3 Phase - 60 Hz

CSL104

Voltage

208/230

460

575

 

 

 

 

FLA

3.5

1.7

1.4

 

 

 

 

WSA

4.4

2.1

1.8

 

 

 

 

OPD

15.0

15.0

15.0

 

 

 

 

* Contact factory for 380-3-60 data.

Table 25 Liebert Lee-Temp receiver heater pads for use w/CSL condensers

Volts

120

230

 

 

 

Watts/Pad

150

150

 

 

 

FLA

1.4

0.7

 

 

 

WSA

1.8

0.9

 

 

 

OPD

15

15

 

 

 

Separate electrical source required for continuous operation of single phase heater pads for Liebert Lee-Temp.

Table 26 Drycooler and pump package - 95°F (35°C) ambient *

Voltage

208/230

460

575

 

 

 

 

Glycol

 

 

 

 

 

 

 

DSF Model

112

112

112

 

 

 

 

Pump Hp

3/4

3/4

3/4

 

 

 

 

FLA

7.0

3.3

2.7

 

 

 

 

WSA

7.9

3.7

3.1

 

 

 

 

OPD

15

15.0

15.0

 

 

 

 

Glycol DS0174

 

 

 

 

 

 

 

DSF Model

174

174

174

 

 

 

 

Pump Hp

1.5

1.5

1.5

 

 

 

 

FLA

13.6

6.4

5.2

 

 

 

 

WSA

15.3

7.2

5.8

 

 

 

 

OPD

20

15.0

15.0

 

 

 

 

GLYCOOL

 

 

 

 

 

 

 

DSO Model

112

112

112

 

 

 

 

Pump Hp

1-1/2

1-1/2

1-1/2

 

 

 

 

FLA

10.1

4.7

3.8

 

 

 

 

WSA

11.8

5.5

4.4

 

 

 

 

OPD

15

15

15

 

 

 

 

1.Pump and drycooler powered from same 3 phase feeder. * Contact factory for 380-3-60 data.

47

Page 55
Image 55
Emerson ITR manual Fan speed control condensers, Liebert Lee-Temp condensers, Drycooler and pump package 95F 35C ambient