Electrical Data

Table 30 Outdoor condensing units

Electrical Data 50 Hz 35°C (95°F) Ambient

 

 

 

Voltage

Model

PFH066A-_L

 

 

 

200/230-3-50

FLA

24.1

 

 

 

380/415-3-50

FLA

13.2

 

 

 

Electrical Data 50 Hz 40°C (105°F) Ambient

 

 

 

Voltage

Model

PFH066A-_H

 

 

 

200/230-3-50

FLA

24.2

 

 

 

380/415-3-50

FLA

13.2

 

 

 

Electrical Data 50 Hz Quiet-Line 35°C (95°F)

 

 

 

Voltage

Model

PFHZ66A-_L

 

 

 

200/230-3-50

FLA

22.5

 

 

 

380/415-3-50

FLA

12.4

 

 

 

Table 31 Indoor condensing units air-cooled

Electrical Data 50 Hz 35°C (95°F) Ambient

Voltage

Model

 

MC_64A

 

 

 

 

380/415-3-50

FLA

 

13.7

 

 

 

 

1. Consult factory for 200/230 volts.

 

Table 32 Indoor condensing units water-cooled

Voltage

Model

MC_68W

 

 

 

380/415-3-50

FLA

10.0

 

 

 

1. Consult factory for 200/230 volts.

Table 33 Fan speed control condensers

35°C (95°F) Ambient (1 Phase - 50 Hz)

CSF104

Voltage

FLA

200/230

4.0

Table 34 Liebert Lee-Temp condensers

35°C (95°F) Ambient (3 Phase - 50 Hz)

CSL104

Voltage

200/230

380/ 415

 

 

 

FLA

3.5

1.7

 

 

 

Table 35 Liebert Lee-Temp receiver heater pads; for use w/CSL condensers

Volts

230

 

 

Watts/Pad

150

 

 

FLA

0.7

 

 

Separate electrical source required for continuous operation of single phase heater pads for Liebert Lee-Temp.