Electrical Data

15.0ELECTRICAL DATA

Table 16

Liebert Challenger ITR electrical data1—60 Hz

 

 

 

 

 

 

 

 

 

 

 

Self-Contained

 

 

 

 

Split System Evaporator or Chilled Water

 

 

 

 

 

 

 

 

 

 

Model Type

 

 

BR067A, BR071WG, BM061G

 

 

 

BR060E, BR102C

 

 

 

 

 

 

 

All Voltages Are 3 Phase Unless Noted Otherwise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

208

 

230

460

 

575

 

208

 

230

 

460

 

575

With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note: See Table 17 for units w/SCR reheats.2)

 

 

 

Motor

 

 

 

1.5 hp (1.1 kW)

 

 

 

 

 

1.5 hp (1.1 kW)

 

 

FLA

68.0

 

65.0

32.3

 

24.6

 

60.6

 

55.4

 

28.1

 

24.6

 

WSA

83.6

 

80.0

39.7

 

30.8

 

75.8

 

69.3

 

35.1

 

30.8

 

OPD

90

 

90

40

 

30

 

80

 

70

 

40

 

35

Motor

 

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

69.8

 

66.6

33.1

 

25.2

 

62.4

 

57.0

 

28.9

 

25.2

 

WSA

85.4

 

81.6

40.5

 

31.5

 

78.0

 

71.3

 

36.1

 

31.5

 

OPD

90

 

90

45

 

30

 

80

 

80

 

40

 

35

Motor

 

 

 

3.0 hp

(2.2 kW)

 

 

 

 

 

3.0 hp

(2.2 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

72.9

 

69.4

34.5

 

26.4

 

65.5

 

59.8

 

30.3

 

26.4

 

WSA

88.5

 

84.4

41.9

 

33.0

 

81.9

 

74.8

 

37.9

 

33.0

 

OPD

90

 

90

45

 

35

 

90

 

80

 

40

 

35

Humidifier Only (Infrared

or Steam

Generating)

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

1.5 hp (1.1 kW)

 

 

 

 

 

1.5 hp (1.1 kW)

 

 

FLA

39.7

 

37.0

18.4

 

16.9

 

19.0

 

16.3

 

8.4

 

9.5

 

WSA

44.9

 

42.2

20.9

 

18.8

 

23.8

 

20.4

 

10.5

 

11.9

 

OPD

60

 

60

30

 

25

 

25

 

20

 

15

 

15

Motor

 

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

2.0 hp

(1.5 kW)

 

 

 

FLA

41.5

 

38.6

19.2

 

17.5

 

20.8

 

17.9

 

9.2

 

10.1

 

WSA

46.7

 

43.8

21.7

 

19.4

 

26.0

 

22.4

 

11.5

 

12.6

 

OPD

60

 

60

30

 

25

 

30

 

25

 

15

 

15

Motor

 

 

 

3.0 hp

(2.2 kW)

 

 

 

 

 

3.0 hp

(2.2 kW)

 

 

 

FLA

44.6

41.4

20.6

18.7

 

23.9

20.7

 

10.6

 

11.3

 

WSA

49.8

46.6

23.1

20.6

 

29.9

25.9

 

13.3

 

14.1

 

OPD

70

60

30

25

 

35

30

 

15

 

15

Electric Reheat Only (Note: See Table 17 for Self-contained units w/SCR reheats.2)

Motor

 

1.5 hp (1.1 kW)

 

 

1.5 hp (1.1 kW)

 

FLA

68.0

65.0

32.3

24.6

47.3

44.3

22.3

17.2

WSA

83.6

80.0

39.7

30.2

59.1

55.4

27.9

21.5

OPD

90

90

40

30

60

60

30

25

Motor

 

2.0 hp

(1.5 kW)

 

 

2.0 hp

(1.5 kW)

 

FLA

69.8

66.6

33.1

25.2

49.1

45.9

23.1

17.8

WSA

85.4

81.6

40.5

30.8

61.4

57.4

28.9

22.3

OPD

90

90

45

30

70

60

30

25

Motor

 

3.0 hp

(2.2 kW)

 

 

3.0 hp

(2.2 kW)

 

FLA

72.9

69.4

34.5

26.4

52.2

48.7

24.5

19.0

WSA

88.5

84.4

41.9

32.0

65.3

60.9

30.6

23.8

OPD

90

90

45

35

60

70

35

20

Without Electric Reheat

and Humidifier

 

 

 

 

 

 

 

Motor

 

1.5 hp (1.1 kW)

 

 

1.5 hp (1.1 kW)

 

FLA

26.4

25.9

12.6

9.5

5.7

5.2

2.6

2.1

WSA

31.6

31.1

15.1

11.4

7.1

6.5

3.3

2.6

OPD

50

50

25

15

15

15

15

15

Motor

 

2.0 hp

(1.5 kW)

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

 

 

 

 

 

FLA

28.2

27.5

13.4

10.1

7.5

6.8

3.4

2.7

WSA

33.4

32.7

15.9

12.0

9.4

8.5

4.3

3.4

OPD

50

50

25

15

15

15

15

15

Motor

 

3.0 hp

(2.2 kW)

 

 

3.0 hp

(2.2 kW)

 

FLA

31.3

30.3

14.8

11.3

10.6

9.6

4.8

3.9

WSA

36.5

35.5

17.3

13.2

13.3

12.0

6.0

4.9

OPD

50

50

25

20

20

20

15

15

1.Contact factory for 380-3-60 data.

2.For Split System Evaporators with SCR reheat, use the values above. The values above were calculated per UL Standard 1995.

FLA = Full Load Amps (Input Amps); WSA = Wire Size Amps (Minimum Supply Circuit Ampacity); OPD = Maximum Overcurrent Protective Device Size RLA = Rated Load Amps; LRA = Locked Rotor Amps

* R = In the Row; M = In the Row with Econ-O-Coil

43

Page 51
Image 51
Emerson manual Electrical Data, Liebert Challenger ITR electrical data1-60 Hz