System Data

Table 8

Liebert Challenger ITR water cooled data, 50 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Type

BR = Horizontal Flow

 

Self-Contained

Split Systems

 

 

Indoor Unit

 

 

 

BR 070WG

 

BR 059E

 

 

 

 

 

 

 

 

Net Capacity Data

 

kW

 

BTU/H

kW

 

BTU/H

 

 

 

 

 

 

 

 

37.8ºC DB, 21.1ºC WB (100ºF DB, 70ºF WB) 20% RH

 

 

 

 

 

 

 

 

Total

 

24.0

 

81,800

23.1

 

78,800

 

 

 

 

 

 

 

 

 

 

Sensible

 

24.0

 

81,800

23.1

 

78,800

 

Non Standard Flow Rates

 

 

2500 CFM

 

2400 CFM

35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24% RH

 

 

 

 

 

 

 

Total

 

23.0

 

78,500

22.4

 

76,500

 

Sensible

 

23.0

 

78,500

22.4

 

76,500

32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH

 

 

 

 

 

 

 

Total

 

21.8

 

74,300

21.2

 

72,400

 

 

 

 

 

 

 

 

 

 

Sensible

 

21.8

 

74,300

21.2

 

72,400

 

 

 

 

 

 

 

 

29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

20.6

 

70,200

20.0

 

68,300

 

Sensible

 

20.6

 

70,200

20.0

 

68,300

26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH

 

 

 

 

 

 

 

Total

 

19.4

 

66,200

18.9

 

64,500

 

Sensible

 

19.4

 

66,200

18.9

 

64,500

 

 

 

 

 

 

 

 

26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

20.0

 

68,400

19.4

 

66,100

 

 

 

 

 

 

 

 

 

 

Sensible

 

15.6

 

53,100

15.3

 

52,300

23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH

 

 

 

 

 

 

 

Total

 

18.6

 

63,500

18.0

 

61,400

 

Sensible

 

15.1

 

51,500

14.8

 

50,600

23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH

 

 

 

 

 

 

 

Total

 

18.1

 

61,800

17.5

 

59,800

 

 

 

 

 

 

 

 

 

 

Sensible

 

16.1

 

55,100

15.9

 

54,300

22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.8

 

60,700

17.2

 

58,700

 

Sensible

 

14.8

 

50,400

14.5

 

49,600

22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH

 

 

 

 

 

 

 

Total

 

17.3

 

59,200

16.8

 

57,400

 

Sensible

 

15.8

 

53,900

15.6

 

53,100

Fan Data (Blower A12x9AT)**

 

 

 

 

 

 

 

Standard Air, CMH (CFM)

 

 

4420 (2600)

 

4420 (2600)

 

 

 

 

 

 

 

 

Standard Fan Motor, kW (hp)

 

 

1.1 (1-1/2)

 

1.1 (1-1/2)

 

Opt Fan Motor, kW (hp)

 

 

1.5 (2)

 

1.5 (2)

 

Ext Static Pa, (in. WG)

 

 

75 (.3)

 

75 (.3)

Evaporator Coil (V-Frame, at standard conditions)

 

 

 

 

 

 

 

Face Area, m2 (ft.2)

 

 

.62 (6.67)

 

.62 (6.67)

 

Rows

 

 

4

 

4

 

 

 

 

 

 

 

 

Face Velocity, m/s (FPM)

 

 

1.9 (375)

 

1.9 (375)

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard

 

 

 

 

 

 

 

Capacity, element kW (inc. motor heat, BTU/H)

 

 

15 (56,200)

 

15 (56,200)

Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Optional (includes std air volume and opt fan motor hp)

 

Capacity, inc. motor heat, kW (BTU/H)

 

 

25.3 (86,200)

 

25.3 (86,200)

 

Flow Rate, l/s (GPM)

 

 

.32 (5.0)

 

.32 (5.0)

 

Pressure drop, kPa (ft.)

 

 

50.4 (16.9)

 

50.4 (16.9)

Hot Gas Reheat - Optional (includes standard air volume and optional fan motor)

 

 

 

 

Capacity, inc. motor heat, kW (BTU/H)

 

 

15.0 (51,300)

 

15.0 (51,300)

 

 

 

 

 

 

 

 

 

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

30

Page 38
Image 38
Emerson manual Liebert Challenger ITR water cooled data, 50 Hz, Btu/H