Emerson ITR manual Self-contained with SCR reheat, Motor Hp 1.5 kW, Motor Hp 2.2 kW

Models: ITR

1 74
Download 74 pages 51.84 Kb
Page 52
Image 52

Electrical Data

Table 17 Self-contained with SCR reheat *

Voltage (3, 60 Hz)

208

230

460

575

 

 

 

 

 

Electric Reheat and Humidifier (Infrared or Steam

 

Generating)

 

 

 

 

Motor

 

1.5 hp (1.1 kW)

 

 

 

 

 

 

FLA

81.3

76.1

38.1

N/A

 

 

 

 

 

WSA

96.9

91.1

45.5

N/A

 

 

 

 

 

OPD

100

100

50

N/A

 

 

 

 

 

Motor

 

2.0 hp (1.5 kW)

 

 

 

 

 

 

FLA

83.1

77.7

38.9

N/A

 

 

 

 

 

WSA

98.7

92.7

46.3

N/A

 

 

 

 

 

OPD

100

100

50

N/A

 

 

 

 

 

Motor

 

3.0 hp (2.2 kW)

 

 

 

 

 

 

FLA

86.2

80.5

40.3

N/A

 

 

 

 

 

WSA

101.8

95.5

47.7

N/A

 

 

 

 

 

OPD

110

100

50

N/A

 

 

 

 

 

Electric Reheat Only

 

 

 

 

 

 

 

 

 

Motor

 

1.5 hp (1.1 kW)

 

 

 

 

 

 

FLA

68.0

65.0

32.3

N/A

 

 

 

 

 

WSA

83.6

80.0

39.7

N/A

 

 

 

 

 

OPD

90

90

40

N/A

 

 

 

 

 

Motor

 

2.0 hp (1.5 kW)

 

 

 

 

 

 

FLA

69.8

66.6

33.1

N/A

 

 

 

 

 

WSA

85.4

81.6

40.5

N/A

 

 

 

 

 

OPD

90

90

45

N/A

 

 

 

 

 

Motor

 

3.0 hp (2.2 kW)

 

 

 

 

 

 

FLA

72.9

69.4

34.5

N/A

 

 

 

 

 

WSA

88.5

84.4

41.9

N/A

 

 

 

 

 

OPD

90

90

45

N/A

 

 

 

 

 

Note: Compressor is locked on. Heater is same size as standard. * Contact factory for 380-3-60 data.