Emerson manual Liebert Challenger ITR chilled water data, 60 Hz

Models: ITR

1 74
Download 74 pages 51.84 Kb
Page 44
Image 44

System Data

Table 14 Liebert Challenger ITR chilled water data, 60 Hz

Capacity Data BTU/H (kW) @ 45°F (7.2°C) EWT, 10°F (5.6°C) Water Rise; Net Capacity Data

Indoor Unit

 

 

 

 

BR = Horizontal Flow

BR 102C

 

100ºF DB, 70ºF WB (37.8ºC DB, 21.1ºC WB) 20% RH, 12°F

 

(6.7°C) Water Rise

 

 

 

 

Total

BTU/H (kW)

125,000

 

36.6

Sensible

BTU/H (kW)

118,000

 

34.6

Flow Rate

GPM (l/s)

21.4

 

1.4

Pressure Drop

ft (kPa)

25.5

 

76.0

95ºF DB, 68.3ºF WB (35ºC DB, 20.2ºC WB) 24% RH, 12°F

 

(6.7°C) Water Rise

 

 

 

 

Total

BTU/H (kW)

113,000

 

33.1

Sensible

BTU/H (kW)

107,000

 

31.4

Flow Rate

GPM (l/s)

19.6

 

1.2

Pressure Drop

ft (kPa)

21.7

 

64.7

90ºF DB, 66.5ºF WB (32.2ºC DB, 19.2ºC WB) 28% RH, 12°F (6.7°C)

Water Rise

 

 

 

 

Total

BTU/H (kW)

101,000

 

29.6

Sensible

BTU/H (kW)

94,700

 

27.7

Flow Rate

GPM (l/s)

17.4

 

1.1

Pressure Drop

ft (kPa)

17.4

 

51.9

85ºF DB, 64.4ºF WB (29.4ºC DB, 18ºC WB) 32% RH

 

Total

BTU/H (kW)

91,000

 

26.7

Sensible

BTU/H (kW)

85,000

 

24.9

Flow Rate

GPM (l/s)

18.9

 

1.2

Pressure Drop

ft (kPa)

20.2

 

60.2

80ºF DB, 62.7ºF WB (26.7ºC DB, 17.1ºC WB) 38% RH

 

Total

BTU/H (kW)

79,000

 

23.1

Sensible

BTU/H (kW)

72,400

 

21.2

 

 

 

 

 

Flow Rate

GPM (l/s)

16.5

 

1.0

 

 

 

 

 

Pressure Drop

ft (kPa)

15.8

 

47.1

80ºF DB, 66.5ºF WB (26.7ºC DB, 19.2ºC WB) 50% RH

 

Total

BTU/H (kW)

98,200

 

28.8

Sensible

BTU/H (kW)

71,500

 

20.9

Flow Rate

GPM (l/s)

19.7

 

1.2

Pressure Drop

ft (kPa)

22.1

 

65.9

75ºF DB, 62.5ºF WB (23.9ºC DB, 16.9ºC WB) 50% RH

 

Total

BTU/H (kW)

72,900

 

21.4

Sensible

BTU/H (kW)

61,000

 

17.9

Flow Rate

GPM (l/s)

14.7

 

0.9

Pressure Drop

ft (kPa)

12.8

 

38.1

75ºF DB, 61.1ºF WB (23.9ºC DB, 16.2ºC WB) 45% RH

 

Total

BTU/H (kW)

68,200

 

20.0

Sensible

BTU/H (kW)

63,100

 

18.5

Flow Rate

GPM (l/s)

13.3

 

0.8

Pressure Drop

ft (kPa)

10.6

 

31.6

72ºF DB, 60.1ºF WB (22.2ºC DB, 15.6ºC WB) 50% RH

 

Total

BTU/H (kW)

59,900

 

17.6

Sensible

BTU/H (kW)

54,400

 

15.9

Flow Rate

GPM (l/s)

12.0

 

0.8

Pressure Drop

ft (kPa)

8.8

 

26.2

72ºF DB, 58.7ºF WB (22.2ºC DB, 14.8ºC WB) 45% RH

 

Total

BTU/H (kW)

56,200

 

16.5

Sensible

BTU/H (kW)

55,300

 

16.2

Flow Rate

GPM (l/s)

11.1

 

0.7

Pressure Drop

ft (kPa)

7.6

 

22.6

Indoor Unit

BR 102C

Fan Data (Blower A12x9AT)**

 

 

 

Standard Air, CFM (CMH)

2800 (4760)

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

Opt. Fan Motor, hp (kW)

2 (1.5)

Ext Static, in. WG (Pa)

.3 (75)

Chilled Water Coil (V-Frame, at standard conditions)

 

 

Face Area, ft.2 (m2)

6.67 (.62)

Rows

4

Face Velocity, FPM (m/s)

405 (2.1)

Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Std

Capacity, inc. motor heat, BTU/H (element kW)

56,200 (15)

 

 

Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)

Capacity, inc. motor heat, BTU/H (kW)

88,700 (26.0)

Flow Rate, GPM (l/s)

5.0

(.32)

Pressure drop, ft. (kPa)

16.9

(50.4)

Infrared Humidifier - Standard

 

 

Capacity, lb/hr (kg/hr)

11 (5)

kW

4.8

Steam Generating Humidifier - Optional

 

 

Capacity, lb/hr (kg/hr)

11 (5)

kW

3.9

Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type

20% Eff. available in 2" (51mm) - Std, or Opt 4" (102mm) Depths; other Optional 4" (102mm) Eff. are: 30%, 40-45%, 60-65%

Nominal Size - in (mm)

28.5 x 29.5

(724 x 749)

 

 

Effective Surface Area, ft2 (m2)

24.1 (2.2)

Connection Sizes Challenger ITR Unit

 

CW Supply

1-1/8 OD Cu

CW Return

1-1/8 OD Cu

Humidifier Supply

1/4 OD Cu

Condensate Drain

1/2 FPT

Control Valve

 

Maximum design water pressure 150 psi (1034.3 kPa)

Valve Actuator

Modulating

Sensors

Proportional

Valve Body

Three-Way

Valve Size, inches

1

Cv

13.9

Two-Way Valve (Optional)

 

Close-Off Pressure, PSI (kPa)

70 (483)

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

36

Page 44
Image 44
Emerson manual Liebert Challenger ITR chilled water data, 60 Hz, Indoor Unit BR 102C Fan Data Blower A12x9AT