System Data

Table 7

Liebert Challenger ITR water cooled data, 60 Hz (continued)

 

 

 

 

System Type

Self-Contained

Split Systems

 

 

 

Indoor Unit

BR 071WG

BR 060E

 

 

 

Infrared Humidifier - Standard

 

 

 

 

 

 

 

Capacity, lb/hr (kg/hr)

11 (5)

11 (5)

 

 

 

 

 

kW

4.8

4.8

 

 

 

Steam Generating Humidifier - Optional

 

 

 

 

 

 

 

Capacity, lb/hr (kg/hr)

11 (5)

11 (5)

 

 

 

 

 

kW

3.9

3.9

 

 

 

Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type

 

 

 

20% efficiencies available in 2" (51mm) - Standard, or optional 4" (102mm) depths; other optional 4" (102mm) efficiencies

are: 30%, 40-45%, 60-65%

 

 

 

Nominal Size, in. (mm)

28.5 x 29.5

28.5 x 29.5

 

(724 x 749)

(724 x 749)

 

 

 

Effective Surface Area, ft2 (m2)

24.1 (2.2)

24.1 (2.2)

Water Regulating Valve

 

 

 

 

 

 

 

Size, in.

1

1

 

 

 

Water Requirements (Coaxial Condenser)

 

MC_69W

 

 

 

 

 

THR - BTU/H (kW) @ 75°F (22.2°C), 50% RH

82,000 (24.0)

81100 (23.8)

 

 

 

65°F (18.3°C) EWT - 105°F (40.6°C) Cond Temp

 

 

 

 

 

 

 

Flow Rate, GPM (l/s)

5.4 (.34)

5.4 (.34)

 

 

 

 

 

Pressure Drop, PSI (kPa)

0.9 (6.2)

1.2 (8.1)

 

 

 

75°F (23.9°C) EWT - 105°F (40.6°C) Cond Temp

 

 

 

 

 

 

 

Flow Rate, GPM (l/s)

7.7 (.49)

7.6 (.48)

 

 

 

 

 

Pressure Drop, PSI (kPa)

1.6 (11.0)

2.2 (15.2)

 

 

 

85°F (29.4°C) EWT - 115°F (46.1°C) Cond Temp

 

 

 

 

 

 

 

Flow Rate, GPM (l/s)

9.9 (.62)

9.7 (.61)

 

 

 

 

 

Pressure Drop, PSI (kPa)

2.5 (17.2)

3.5 (24.2)

 

 

 

Connection Sizes Challenger ITR Unit

 

 

 

 

 

 

 

Condenser Supply

1-1/8 OD Cu

 

 

 

 

 

 

Condenser Return

1-1/8 OD Cu

 

 

 

 

 

 

Liquid Line

 

1/2 OD Cu

 

 

 

 

 

Suction Line

 

1 1/8 CD Cu

 

 

 

 

 

Humidifier Supply Line

1/4 OD Cu

1/4 OD Cu

 

 

 

 

 

Condensate Drain Line

1/2 FPT

1/2 FPT

 

 

 

Connection Sizes Remote Condensing Unit

 

 

 

 

 

 

 

Condenser Supply

 

1-1/8 OD Cu

 

 

 

 

 

Condenser Return

 

1-1/8 OD Cu

 

 

 

 

 

Liquid Line

 

1/2 OD Cu

 

 

 

 

 

Suction Line

 

1-1/8 OD Cu

 

 

 

 

Self-contained unit pressure drops based on two-way valve with bypass. Split system unit pressure drops based on two-way or three-way valve.