System Data

Table 10 Liebert Challenger ITR glycol cooled data, 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Type

 

Glycol Cooled

 

 

 

GLYCOOL

 

BR = Horizontal Flow

 

 

 

 

 

 

 

 

 

BM = Horizontal Flow with Econ-O-Coil

Self-Contained

 

Split Systems

Self Contained

Indoor Unit

BR 071WG

 

BR 060E

BM 061G

 

Net Capacity Data

BTU/H

 

kW

BTU/H

 

kW

BTU/H

 

kW

100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH

 

 

 

 

 

 

 

Total

69,800

 

20.5

71,600

 

21.0

66,000

 

19.3

Sensible

69,800

 

20.5

71,600

 

21.0

66,000

 

19.3

Non Standard Flow Rates

1800 CFM, 21.5 GPM,

2100 CFM

2600 CFM, 20.5 GPM,

27.4 FT PD

 

24.6 FT PD

 

 

 

 

 

 

 

95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH

 

 

 

 

 

 

 

Total

68,600

 

20.1

72,300

 

21.2

64,700

 

19.0

Sensible

68,600

 

20.1

72,300

 

21.2

64,700

 

19.0

Non Standard Flow Rates

2100 CFM, 21.5 GPM,

2600 CFM

2300 CFM, 19.5 GPM,

27.4 FT PD

 

22.5 FT PD

 

 

 

 

 

 

 

90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH

 

 

 

 

 

 

 

Total

64,700

 

19.0

69,900

 

20.5

65,300

 

19.1

Sensible

64,700

 

19.0

69,900

 

20.5

65,300

 

19.1

Non Standard Flow Rates

2100CFM,18.5 GPM, 20.9FT PD

 

 

 

19.5 GPM, 22.5 FT PD

85°F DB, 64.4°F WB (29.4°C DB, 18°C WB) 32% RH

 

 

 

 

 

 

 

Total

62,800

 

18.4

66,200

 

19.4

61,500

 

18.0

Sensible

62,800

 

18.4

66,200

 

19.4

61,500

 

18.0

Non Standard Flow Rates

2300 CFM

 

 

 

 

 

 

 

80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH

 

 

 

 

 

 

 

Total

62,400

 

18.3

62,500

 

18.3

58,200

 

17.1

Sensible

62,400

 

18.3

62,500

 

18.3

58,200

 

17.1

80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH

 

 

 

 

 

 

 

Total

62,900

 

18.4

63,000

 

18.5

59,900

 

17.6

Sensible

53,200

 

15.6

53,200

 

15.6

51,200

 

15.0

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH

 

 

 

 

 

 

 

Total

58,900

 

17.3

58,800

 

17.2

55,900

 

16.4

Sensible

51,500

 

15.1

51,500

 

15.1

49,500

 

14.5

75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH

 

 

 

 

 

 

 

Total

59,000

 

17.3

59,000

 

17.3

55,000

 

16.1

Sensible

59,000

 

17.3

59,000

 

17.3

55,000

 

16.1

72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH

 

 

 

 

 

 

 

Total

56,500

 

16.6

56,500

 

16.6

53,600

 

15.7

Sensible

50,500

 

14.8

50,500

 

14.8

48,500

 

14.2

72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH

 

 

 

 

 

 

 

Total

56,900

 

16.7

56,900

 

16.7

53,000

 

15.5

Sensible

56,900

 

16.7

56,900

 

16.7

53,000

 

15.5

GLYCOOL Coil Sensible Capacity

 

 

 

 

 

 

 

 

 

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 45°F (7.2°C) EGT

 

 

 

 

47,700

 

14.0

Fan Data (Blower A12x9AT)**

 

 

 

 

 

 

 

 

 

Standard Air, CFM (CMH)

2800 (4760)

 

2800 (4760)

2800 (4760)

 

Standard Fan Motor, hp (kW)

1-1/2 (1.1)

 

1-1/2 (1.1)

2 (1.5)

 

Opt Fan Motor, hp (kW)

2 (1.5)

 

 

2 (1.5)

 

N/A

 

Ext Static, in. WG (Pa)

.3 (75)

 

 

.3 (75)

 

.3 (75)

 

Evaporator Coil (V-Frame, at standard conditions)

 

 

 

 

 

 

 

Face Area, ft.2 (m2)

6.67 (.62)

 

6.67 (.62)

6.67 (.62)

 

Rows

4

 

 

4

 

4

 

 

Face Velocity, FPM (m/s)

405 (2.1)

 

405 (2.1)

405 (2.1)

 

Electric Reheat 2 Stage (Stainless Steel, Fin

Tubular) - Standard

 

 

 

 

 

 

 

Capacity, inc. motor heat, BTU/H(element kW)

56,200 (15)

 

56,200 (15)

57,700 (15)

 

Hot Water Reheat 180°F (82.2°C) EWT, 75°F

(23.9°C) EAT - Optional (includes standard air volume and optional fan motor hp)

Capacity, inc. motor heat, BTU/H(kW)

88,700 (26.0)

 

88,700 (26.0)

N/A

 

Flow Rate, GPM (l/s)

5.0 (.32)

 

5.0 (.32)

5.0 (.32)

 

Pressure drop, ft. (kPa)

16.9 (50.4)

 

16.9 (50.4)

16.9 (50.4)

 

Hot Gas Reheat - Optional (includes standard

air volume and optional fan motor)

 

 

 

 

 

 

Capacity, inc. motor heat, BTU/H (kW)

54,900 (16.1)

 

54,900 (16.1)

N/A

 

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%. All above data is based on 40% ethylene glycol solution.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

32