Emerson manual Liebert Challenger ITR air-cooled data-50 Hz, System Type Split Systems

Models: ITR

1 74
Download 74 pages 51.84 Kb
Page 34
Image 34

 

 

 

 

 

 

 

 

 

 

System Data

Table 4

Liebert Challenger ITR air-cooled data—50 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Type

 

 

 

 

 

 

 

Split Systems

 

 

BR = Horizontal Flow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w/Outdoor Prop-Fan

w/Indoor Centrifugal

 

 

Self-Contained

 

Condensing Unit

Condensing Unit

 

 

 

 

 

 

 

 

Indoor Unit

 

BR 065A

 

BR 059E

 

BR 059E

 

Net Capacity Data

 

kW

 

BTU/H

 

kW

 

BTU/H

kW

 

BTU/H

 

 

 

 

 

 

 

 

 

 

 

 

37.8°C DB, 21.1°C WB (100°F DB, 70°F WB) 20%

RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

22.4

 

76,300

 

25.8

 

87,900

21.0

 

71,800

 

Sensible

 

22.4

 

76,300

 

25.8

 

87,900

21.0

 

71,800

 

Non Standard Flow Rates

 

2300 CFM

 

 

 

 

2100 CFM

 

35°C DB, 20.2°C WB (95°F DB, 68.3°F WB) 24% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

22.0

 

75,100

 

24.3

 

83,100

21.3

 

72,600

 

Sensible

 

22.0

 

75,100

 

24.3

 

83,100

21.3

 

72,600

32.2°C DB, 19.2°C WB (90°F DB, 66.5°F WB) 28% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

20.9

 

71,200

 

23.0

 

78,400

20.2

 

68,800

 

Sensible

 

20.9

 

71,200

 

23.0

 

78,400

20.2

 

68,800

29.4°C DB, 18°C WB (85°F DB, 64.4°F WB) 32% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

19.7

 

67,200

 

21.6

 

73,800

19.1

 

65,100

 

Sensible

 

19.7

 

67,200

 

21.6

 

73,800

19.1

 

65,100

26.7°C DB, 17.1°C WB (80°F DB, 62.7°F WB) 38% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

18.6

 

63,600

 

20.3

 

69,300

18.0

 

61,400

 

Sensible

 

18.6

 

63,600

 

20.3

 

69,300

18.0

 

61,400

26.7°C DB, 19.2°C WB (80°F DB, 66.5°F WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

19.0

 

64,900

 

21.3

 

72,600

18.3

 

62,400

 

Sensible

 

15.2

 

51,800

 

16.0

 

54,700

14.9

 

50,900

23.9°C DB, 16.9°C WB (75°F DB, 62.5°F WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.8

 

60,600

 

19.5

 

66,600

17.0

 

58,100

 

Sensible

 

14.7

 

50,300

 

15.5

 

52,800

14.4

 

49,300

23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB) 45% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.3

 

59,100

 

19.0

 

64,700

16.6

 

56,700

 

Sensible

 

15.8

 

54,000

 

16.5

 

56,300

15.5

 

53,000

22.2°C DB, 15.6°C WB (72°F DB, 60.1°F WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.0

 

58,100

 

18.6

 

63,600

16.3

 

55,700

 

Sensible

 

14.4

 

49,300

 

15.1

 

51,700

14.2

 

48,300

22.2°C DB, 14.8°C WB (72°F DB, 58.7°F WB) 45% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

16.7

 

56,900

 

18.0

 

61,500

16.3

 

55,700

 

Sensible

 

15.5

 

52,900

 

16.1

 

54,900

16.3

 

55,700

Fan Data (Blower A12x9AT)**

 

 

 

 

 

 

 

 

 

 

 

 

Standard Air, CMH (CFM)

 

4420 (2600)

 

4420 (2600)

4420 (2600)

 

Standard Fan Motor, kW (hp)

 

1.1 (1-1/2)

 

1.1 (1-1/2)

 

1.1 (1-1/2)

 

 

Opt Fan Motor, kW (hp)

 

1.5 (2)

 

 

1.5 (2)

 

1.5 (2)

 

 

Ext Static, Pa (in. WG)

 

75 (.3)

 

 

75 (.3)

 

75 (.3)

 

Evaporator Coil (V-Frame, at Standard

Conditions)

 

 

 

 

 

 

 

 

 

Face Area, m2 (ft.2)

 

.62 (6.67)

 

.62 (6.67)

 

.62 (6.67)

 

 

Rows

 

4

 

 

 

4

 

 

4

 

 

 

Face Velocity, m/s (FPM)

 

1.9 (375)

 

1.9 (375)

 

1.9 (375)

 

Electric Reheat 2 Stage (Stainless Steel,

Fin Tubular) - Standard

 

 

 

 

 

 

 

Capacity, element kW (inc. motor heat, BTU/H)

 

15 (56,200)

 

15 (56,200)

 

15 (56,200)

 

Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Opt. (inc. standard air volume and optional fan motor hp)

 

Capacity, inc. motor heat, kW (BTU/H)

 

25.3 (86,200)

 

25.3 (86,200)

25.3 (86,200)

 

Flow Rate, l/s (GPM)

 

.32 (5.0)

 

.32 (5.0)

 

.32 (5.0)

 

 

Pressure drop, kPa (ft.)

 

50.4 (16.9)

 

50.4 (16.9)

 

50.4 (16.9)

 

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

26

Page 34
Image 34
Emerson manual Liebert Challenger ITR air-cooled data-50 Hz, System Type Split Systems, Fan Data Blower A12x9AT