Emerson manual Liebert Challenger ITR chilled water data, 50 Hz, Indoor Unit BR 101C

Models: ITR

1 74
Download 74 pages 51.84 Kb
Page 45
Image 45

System Data

Table 15 Liebert Challenger ITR chilled water data, 50 Hz

Capacity Data kW (BTU/H) @ 7.2°C (45°F ) EWT, 5.6°C (10°F) Water Rise; Net Capacity Data

Indoor Unit

 

 

BR 101C

BR = Horizontal Flow

 

37.8ºC DB, 21.1ºC WB (100ºF DB,

70ºF WB) 20% RH, 6.7°C (12°F)

Water Rise

 

 

 

 

Total

kW (BTU/H)

34.0

 

116,000

Sensible

kW (BTU/H)

31.9

 

109,000

Flow Rate

l/s (GPM)

1.3

 

19.9

Pressure Drop

kPa (ft)

66.5

 

22.3

35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24% RH,

6.1°C (11°F) Water Rise

 

 

 

Total

kW (BTU/H)

31.1

 

106,000

Sensible

kW (BTU/H)

29.0

 

99,100

Flow Rate

l/s (GPM)

1.3

 

19.9

Pressure Drop

kPa (ft)

66.5

 

22.3

32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH

Total

kW (BTU/H)

28.2

 

96,100

Sensible

kW (BTU/H)

26.0

 

88,900

Flow Rate

l/s (GPM)

1.3

 

20.0

Pressure Drop

kPa (ft)

66.8

 

22.4

29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32% RH

Total

kW (BTU/H)

24.7

 

84,200

Sensible

kW (BTU/H)

23.0

 

78,400

Flow Rate

l/s (GPM)

1.1

 

17.6

Pressure Drop

kPa (ft)

52.7

 

17.7

26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH

Total

kW (BTU/H)

21.5

 

73,500

Sensible

kW (BTU/H)

19.6

 

66,900

 

 

 

 

 

Flow Rate

l/s (GPM)

1.0

 

15.8

 

 

 

 

 

Pressure Drop

kPa (ft)

42.9

 

14.4

26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH

Total

kW (BTU/H)

27.5

 

94,000

Sensible

kW (BTU/H)

19.8

 

67,500

Flow Rate

l/s (GPM)

1.2

 

19.7

Pressure Drop

kPa (ft)

65.9

 

22.1

23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH

Total

kW (BTU/H)

20.4

 

69,700

Sensible

kW (BTU/H)

16.8

 

57,500

Flow Rate

l/s (GPM)

0.9

 

14.7

Pressure Drop

kPa (ft)

38.1

 

12.8

23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH

Total

kW (BTU/H)

19.0

 

64,800

Sensible

kW (BTU/H)

17.4

 

59,500

Flow Rate

l/s (GPM)

0.8

 

13.3

Pressure Drop

kPa (ft)

31.6

 

10.6

22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH

Total

kW (BTU/H)

16.7

 

57,100

Sensible

kW (BTU/H)

15.1

 

51,400

Flow Rate

l/s (GPM)

0.8

 

12.0

Pressure Drop

kPa (ft)

26.2

 

8.8

22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH

Total

kW (BTU/H)

15.7

 

53,500

Sensible

kW (BTU/H)

15.4

 

52,400

Flow Rate

l/s (GPM)

0.7

 

11.1

Pressure Drop

kPa (ft)

22.6

 

7.6

Indoor Unit

BR 101C

Fan Data (Blower A12x9AT)**

 

 

 

Standard Air, CMH (CFM)

4420 (2600)

Standard Fan Motor, kW (hp)

1.1 (1-1/2)

Opt Fan Motor, kW (hp)

1.5 (2)

Ext Static, Pa (in. WG)

75 (.3)

Chilled Water Coil (V-Frame, at standard conditions)

 

 

Face Area, m2 (ft2)

.62 (6.67)

Rows

4

Face Velocity, m/s (FPM)

1.9 (375)

Electric Reheat 2-Stage (Stainless Steel, Fin Tubular) - Std

Capacity, element kW (inc. motor heat, BTU/H)

15 (56,200)

Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Optional (Includes std air volume and opt. fan motor hp)

Capacity, inc. motor heat, kW (BTU/H)

25.3 (86,200)

Flow Rate, l/s (GPM)

.32

(5.0)

Pressure drop, kPa (ft.)

50.4

(16.9)

Infrared Humidifier - Standard

 

 

Capacity, kg/hr (lb/hr)

5 (11)

kW

4.8

Steam Generating Humidifier - Optional

 

 

Capacity, kg/hr (lb/hr)

5 (11)

kW

3.9

Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type

20% Eff. available in 51mm (2") - Standard, or Optional 102mm (4") Depths; other Optional 102mm (4") Eff. are: 30%, 40-45%, 60-65%

Nominal Size - mm

28.5 x 29.5

Nominal Size - inches

724 x 749

Effective Surface Area - m2 (ft2)

2.2 (24.1)

Connection Sizes-Challenger ITR Unit

 

CW Supply

1 1/8 OD Cu

CW Return

1 1/8 OD Cu

Humidifier Supply

1/4 OD Cu

Condensate Drain

1/2 FPT

Control Valve

 

Maximum design water pressure 1034.4 kPa (150 PSI)

Valve Actuator

Modulating

Sensors

Proportional

Valve Body

Three-Way

Valve Size, in.

1

Cv

13.9

Two-Way Valve (Optional)

 

Close Off Pressure - kPa (PSI)

483 (70)

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

37

Page 45
Image 45