System Data

Table 12

Liebert Challenger ITR glycol cooled data, 50 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Type

BR = Horizontal Flow

 

 

 

Glycol Cooled

 

 

 

GLYCOOL

 

 

Self-Contained

 

Split Systems

Self Contained

BM = Horizontal Flow with Econ-O-Coil

 

 

Indoor Unit

 

 

 

BR 070WG

 

 

BR 059E

 

BM 058G

Net Capacity Data

 

kW

 

BTU/H

 

kW

 

BTU/H

kW

 

BTU/H

37.8ºC DB, 21.1ºC WB (100ºF DB, 70ºF WB) 20%

RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

20.3

 

69,300

 

20.8

 

70,900

18.8

 

64,100

 

Sensible

 

20.3

 

69,300

 

20.8

 

70,900

18.8

 

64,100

 

Non Standard Flow Rates

 

1900 CFM,

24.5 GPM

 

 

2100

CFM

2000 CFM,

22.5 GPM

35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24%

RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

19.6

 

66,800

 

20.7

 

70,800

17.8

 

60,600

 

Sensible

 

19.6

 

66,800

 

20.7

 

70,800

17.8

 

60,600

 

Non Standard Flow Rates

 

2000 CFM,

23.5 GPM

 

 

2500

CFM

2000 CFM,

20.5 GPM

32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

18.5

 

63,000

 

19.9

 

67,800

16.8

 

57,300

 

Sensible

 

18.5

 

63,000

 

19.9

 

67,800

16.8

 

57,300

 

Non Standard Flow Rates

 

2000 CFM,

21.5 GPM

 

 

 

 

 

2000

CFM

29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32%

RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.9

 

61,200

 

18.8

 

64,200

16.9

 

57,700

 

Sensible

 

17.9

 

61,200

 

18.8

 

64,200

16.9

 

57,700

 

Non Standard Flow Rates

 

2200 CFM,

19.5 GPM

 

 

 

 

 

2400

CFM

26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.1

 

58,400

 

17.7

 

60,500

16.4

 

55,900

 

Sensible

 

17.1

 

58,400

 

17.7

 

60,500

16.4

 

55,900

 

Non Standard Flow Rates

 

 

2300

CFM

 

 

 

 

 

 

 

26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

17.2

 

58,800

 

18.0

 

61,400

16.8

 

57,400

 

Sensible

 

12.7

 

43,200

 

14.8

 

50,500

13.5

 

46,000

 

Non Standard Flow Rates

 

 

2000

CFM

 

 

 

 

 

2400

CFM

23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

16.7

 

57,000

 

16.8

 

57,200

15.9

 

54,100

 

Sensible

 

14.3

 

48,800

 

14.3

 

48,900

13.7

 

46,800

23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

16.7

 

56,900

 

16.3

 

55,800

15.4

 

52,700

 

Sensible

 

16.7

 

56,900

 

15.4

 

52,600

15.4

 

52,700

22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

16.0

 

54,600

 

16.1

 

54,800

15.2

 

51,800

 

Sensible

 

14.0

 

47,900

 

14.0

 

47,900

13.4

 

45,800

22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH

 

 

 

 

 

 

 

 

 

 

 

Total

 

16.1

 

54,800

 

16.1

 

55,000

14.9

 

50,700

 

Sensible

 

16.1

 

54,800

 

16.1

 

55,000

14.9

 

50,700

GLYCOOL Coil Sensible Capacity

 

 

 

 

 

 

 

 

 

 

 

23.9°C DB, 16.9°C WB (75°F DB, 62.5°C WB) 10°C (45°F) EGT

 

 

 

14

 

47,700.0

Fan Data (Blower A12x9AT)**

 

 

 

 

 

 

 

 

 

 

 

Standard Air, CMH (CFM)

 

 

4420 (2600)

 

 

4420 (2600)

 

4420 (2600)

 

Standard Fan Motor, kW (hp)

 

 

1.1 (1-1/2)

 

 

1.1 (1-1/2)

 

1.5 (2)

 

Optional Fan Motor, kW (hp)

 

 

1.5 (2)

 

 

1.5 (2)

 

N/A

 

Ext Static, Pa (in. WG)

 

 

75 (.3)

 

 

75 (.3)

 

75 (.3)

Evaporator Coil (V-Frame, at standard conditions)

 

 

 

 

 

 

 

 

 

 

 

Face Area, m2 (ft.2)

 

 

.62 (6.67)

 

 

.62 (6.67)

 

.62 (6.67)

 

Rows

 

 

4

 

 

4

 

4

 

Face Velocity, m/s (FPM)

 

 

1.9 (375)

 

 

1.9 (375)

 

1.9 (375)

Electric Reheat 2 Stage (Stainless Steel, Fin

Tubular) - Standard

 

 

 

 

 

 

 

Capacity, element kW (inc. motor heat, BTU/H)

 

 

15 (56,200)

 

 

15 (56,200)

 

15 (56,200)

Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C

(75°F) EAT - Optional (Includes

standard air volume and optional fan motor hp)

Capacity, inc. motor heat, kW (BTU/H)

 

25.3 (86,200)

 

25.3 (86,200)

25.3 (86,200)

 

Flow Rate, l/s (GPM)

 

 

.32 (5.0)

 

 

.32 (5.0)

 

.32 (5.0)

 

Pressure drop, kPa (ft.)

 

 

50.4 (16.9)

 

 

50.4 (16.9)

 

50.4 (16.9)

Hot Gas Reheat - Optional (Includes standard

air volume and optional fan motor)

 

 

 

 

 

 

Capacity, kW (BTU/H) (includes motor heat)

 

15.0 (51,300)

 

15.0 (51,300)

15.0 (51,300)

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%. All data above is based on 40% ethylene glycol solution.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

34

Page 42
Image 42