Operation

Module Shutdown Procedure

Perform a Module Shutdown Procedure when you want to remove power from a UPS module when required for maintenance.

Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.0 - Maintenance.

Use the module Monitor/Mimic Display to determine the operating condition of the UPS module. From the module Master Menu, select the Shutdown Procedures screen. Note that this is a two-page screen.

Figure 68 Module shutdown procedures screen

DOWN :

NEXT PAGE

 

 

 

 

SELECT :

MASTER MENU

© 1989-2003

 

 

SHUTDOWN PROCEDURES

1.If load can not be supported by the remaining modules when this module is taken off line, go to the system control cabinet and select the "LOAD TRANSFER PROCEDURES" screen. Follow the instructions to transfer to bypass.

2.Open the module output breaker by simultaneously pressing the OUTPUT TRIP and CONTROL ENABLE pushbuttons.

3.Open the module battery breaker by simultaneously pressing the BATTERY TRIP and CONTROL ENABLE pushbuttons.

4.Manually open the input breaker by moving the handle to the OFF position.

UP : FIRST PAGE

SELECT : MASTER MENU

© 1989-2003

SHUTDOWN PROCEDURES (Cont'd)

5.Verify breaker status on the "MONITOR / MIMIC" screen.

6.If necessary for maintenance purposes, turn the control power switch (fuse disconnect on some models) to the OFF position.

7.Wait a minimum of two (2) minutes before attempting any other action.

Step 1. If the UPS module is on-line, simultaneously press the Output Trip and Control Enable pads (Figure 10). This will open the UPS module output circuit breaker (CB2, Figure 8).

Step 2. Open the module battery disconnect (MBD) circuit breaker by simultaneously pressing the Battery Trip and Control Enable pads (Figure 10).

Step 3. Open the UPS input circuit breaker by moving the handle to the OFF position (Figure 8).

Return to the Monitor/Mimic Display to verify status of the circuit breakers. Press the Alarm Reset pad to clear alarm messages.

Step 4. If maintenance is required on the UPS controls, turn the Control Power switch to the OFF position (Figure 8). You may also want to open the Rectifier Input Breaker (RIB), external to the UPS cabinet.

! WARNING

Lethal voltages are present within this unit even when it is not on or when utility is not being supplied. Observe all cautions and warnings in this manual. Failure to do so could result in serious injury or death. Do not work on or operate this equipment unless you are fully qualified to do so! Never work alone.

Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.0 - Maintenance.

94

Page 100
Image 100
Emerson Series 610 manual Module Shutdown Procedure, Module shutdown procedures screen

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.