Emerson Series 610 manual Detection of Trouble, Torque Requirements

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 112
Image 112
4.4.2Torque Requirements

Maintenance

4.4.2Torque Requirements

All electrical connections must be tight. Table 15 provides the torque values for the connections in the UPS. Use these values unless the equipment is labeled otherwise.

NOTE

Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for the proper torque values required for the battery.

Table 15 Torque specifications (unless otherwise labeled)

Nut And Bolt Combinations

 

 

Grade 2

 

Electrical Connections

 

Standard

 

with Belleville Washers

Bolt Shaft Size

 

 

 

 

 

 

Lb-in

 

 

N-m

Lb-in

N-m

 

 

 

 

 

 

 

1/4

53

 

 

6.0

46

5.2

 

 

 

 

 

 

 

5/16

107

 

 

12

60

6.8

 

 

 

 

 

 

 

3/8

192

 

 

22

95

11

 

 

 

 

 

 

 

1/2

428

 

 

48

256

29

 

 

 

 

 

 

 

 

Circuit Breakers with Compression Lugs (For Power Wiring)

 

 

 

 

 

 

 

 

 

Current Rating

Lb-in

 

 

N-m

 

 

 

 

 

 

 

 

 

400 - 1200 Amps

300

 

 

34

 

 

 

 

 

 

 

 

 

 

Circuit Breakers with Compression Lugs (For Control Wiring)

 

 

 

 

 

 

 

 

 

AWG Wire Size or Range

Lb-in

 

 

N-m

 

 

 

 

 

 

 

 

#22 - #14

3.5 to 5.3

 

0.4 to 0.6

 

 

 

 

 

 

 

 

 

4.5Detection of Trouble

It is important that the operator check the instrument readings if abnormal equipment performance is suspected. Any metered value that differs appreciably from normal could mean an impending mal- function and should be investigated.

Items to check include:

Output voltage of all phases should be within 2% of normal voltage. Output currents on each phase should not normally differ by more than 20%. If a greater difference is noted, the load is unbalanced and corrective action should be taken to redistribute the load, if possible.

If the UPS has not operated on battery power during the last 10 hours, the batteries should require little charging current. Battery mimic should indicate normal DC voltage with the battery charge current no more than 31 Amperes.

Input current on each phase should be within 10% of the average input current.

Alarm messages indicate malfunction or impending malfunction. A daily check of the Operator Control Panel will help to provide an early detection of problems. Refer to Table 9 and Table 10 to interpret alarm messages.

Tracing a problem to a particular section is facilitated by alarm messages and the metered parameter indications. These are stored in the Status Reports and can be displayed at the Opera- tor Control Panel or at an optional terminal. A Liebert Global Services engineer will be familiar with test points inside the unit.

NOTE

If the UPS system has a blown fuse, determine the cause should be determined before replacing the fuse. Contact Liebert Global Services for assistance.

106

Page 112
Image 112
Emerson Series 610 manual Detection of Trouble, Torque Requirements, Torque specifications unless otherwise labeled