Operation

Table 9

Alarm messages - meaning and corrective action (continued)

Alarm

 

 

Cabinet

Special

 

Message

 

Location

Functions

Meaning and Corrective Action

BYPASS (Cont’d.)

 

 

 

Auto Transfer to

 

 

 

The critical load has been automatically transferred to the bypass line.

 

SCC

D, E, F

Use the History Status screen to determine the cause for the transfer.

Bypass

 

 

Clear all of the alarms before attempting to retransfer the load from

 

 

 

 

 

 

 

 

 

bypass to UPS.

Auto Retransfer

 

 

 

An automatic retransfer will be initiated when the OK to Transfer condition

 

SCC

has been present for 10 seconds, if the overload has dropped below

Primed

 

 

 

 

 

 

100% of the rated SCC current and if enough UPS modules are on-line.

 

 

 

 

 

 

 

 

 

 

A manual retransfer is required. Either a system overload condition has

Manual Reset/

 

 

 

lasted more than 5 minutes or no more auto-retransfer attempts are

 

SCC

available. Note that this alarm is only used if auto-retransfer attempts are

Retransfer

 

 

 

 

 

 

enabled.

 

 

 

 

 

 

 

 

 

 

Perform a manual retransfer if all necessary conditions are present.

 

 

 

 

 

The UPS output is not synchronized to the bypass power source. The

 

 

 

 

 

static bypass switch is disconnected or it has failed internally.

Static Switch

 

SCC

D, S

Emergency and overload transfer to the bypass source is not available.

 

Manually set the Static Switch Disconnects to ON (closed) if the static

Unable

 

 

 

 

 

 

switch is disconnected. If the alarm conditions are automatically

 

 

 

 

 

 

 

 

 

 

corrected, reset the alarm to clear it. Contact Liebert Global Services if the

 

 

 

 

 

alarm stays on.

Bypass Not

 

 

SCC

The bypass power source voltage is not within specifications.

Available

 

 

Correct the bypass AC power source.

 

 

 

 

 

 

 

 

 

The power conductors on the bypass line are not wired to the UPS in the

 

 

 

 

 

required sequence. This alarm should appear only during initial start-up or

Bypass Phase

 

SCC

D, L, S

after a repair to the source power system.

Sequence Wrong

Disconnect power from the bypass line and correct the wiring. A Liebert

 

 

 

 

 

 

 

Global Services representative must be present during initial start-up of

 

 

 

 

 

your UPS System.]

 

 

 

 

 

UPS output or system bypass breakers trip failure detected. Critical load

Transfer Fail

 

 

SCC

D, F, L, S

will be transferred to bypass and UPS modules shutdown for isolation

 

 

 

 

 

from bypass source. Contact Liebert Global Services at once.

UPS SYSTEM

 

 

 

 

Input Current

 

 

 

At least one input phase differs from the average current by 10% or more

 

MMU

D, E

for four (4) hours. Contact Liebert Global Services. If the condition

Unbalance

 

 

 

 

 

 

persists, transfer the load to the bypass line.

 

 

 

 

 

 

 

 

SCC

D, L, S

The logic control power supply from the UPS output is not operating

Control Power

 

 

 

properly. The UPS module continues operating but will shut down if the

Fail

 

 

MMU

D, L, S

input power fails. The SCC continues operating but will shut down if the

 

 

 

 

 

bypass power fails. Contact Liebert Global Services immediately.

Output Over/

 

SCC

D, L, S

Output frequency differs from the nominal (60 Hz) by more than 0.5 Hz.

Under Frequency

No transfer or shutdown occurs. Contact Liebert Global Services at once.

 

 

 

 

 

 

 

The UPS system output voltage is under the minimum (-12%) deviation

Output

 

 

SCC

D, F, L, S

from nominal. The load automatically transfers to the bypass line.

 

 

If the alarm condition is no longer present, reset the alarm and retransfer

Undervoltage

 

 

 

 

the load from bypass to UPS. Contact Liebert Global Services if alarm

 

 

 

 

 

 

 

 

 

 

persists.

Output

 

 

 

 

The UPS system output voltage is above the maximum (+10%) deviation

 

 

SCC

D, F, L, S

from nominal. The load automatically transfers to the bypass line. All UPS

Overvoltage

 

 

modules are taken off-line and are shut down. Contact Liebert Global

 

 

 

 

 

 

 

 

 

Services at once. Do not attempt to reset circuit breakers.

 

 

 

SCC

D, R, S

The UPS output current exceeds the rated system load current. This

Overload

 

 

 

 

condition causes an alarm only, the UPS does not shut down.

 

 

 

 

 

 

MMU

D, S

Determine cause of the overload. Reduce the load until the overload

 

 

 

 

 

 

 

 

condition is corrected. Reset the UPS alarm.

Table 9 Abbreviations

 

 

 

D = auto-dial;

 

L = latches

 

 

E = logs only;

 

R = remote

 

 

F = freezes;

 

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

66

Page 72
Image 72
Emerson Series 610 Auto Retransfer, Primed, Manual Reset, Static Switch, Unable, Bypass Not, Available, Bypass Phase

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.