Emerson Series 610 manual

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 91
Image 91
Step 1. Before you apply power to the UPS modules, determine the position of the following circuit breakers and switches:

Operation

Step 1. Before you apply power to the UPS modules, determine the position of the following circuit breakers and switches:

a.Bypass Input Breaker (BIB) - If this circuit breaker is closed, you may already have power to the critical load through the bypass line. If this breaker is closed, leave it closed. If it is open, leave it open until you are ready to energize the bypass line.

b.System Bypass Circuit Breaker (SBB) - This motorized circuit breaker (Figure 9) should be closed unless you are recovering from a Remote Emergency Power Off. You may already be supplying power to the critical load through this breaker. If this breaker is open, you will be instructed to reset it later in this procedure.

c.UPS Output Circuit Breaker - This motorized circuit breaker (see Figure 9) should be open.

d.Static Switch Disconnect - This manually operated disconnect (see Figure 9) will be in the ON (closed) position unless you are recovering from a shutdown. If the disconnect is OFF (open), you will be instructed to reset it and turn it on later in this procedure.

NOTE

Depending on SCC model, the static switch disconnects can be one or two circuit breakers or two contactors. The location could be at the front, right or rear of the cabinet. Refer to the drawing of the SCC cabinet selected for your UPS system.

NOTE

If the system was shut down in response to an “Emergency Off, there may be alarm messages on the LCD screen that describe system conditions before (or at the time of) the shutdown. Some or all of the alarm conditions may have already been resolved. To clear these alarm messages, turn off the control power (see Figure 8 and Figure 9). Wait at least 10 minutes for the control power circuitry to completely de-energize. After 10 minutes, turn control power back on and wait two minutes before continuing.

e. Control Power - The fuses for the SCC control power (labeled F7 through F10, located below the SCC control boards in Figure 9) should be ON (pushed in) unless you are recovering from a maintenance shutdown. If control power is OFF (fuseholders pulled open), leave it OFF until you are ready to apply power to the UPS controls.

! CAUTION

If you are recovering from a UPS system shutdown for maintenance procedures, verify that all of the SCC doors are closed and latched. All test equipment must be removed from the system. All electrical connections must be secure.

Power must be provided to the UPS controls so the operator can use the LCD and so the system logic can perform its control functions. Note that you can use the LCD to monitor UPS system status, even when the UPS modules are not operating.

During a start-up procedure, power is supplied to the critical load through the UPS (internal) bypass line while the UPS modules are being energized. Depending on the reason for your UPS system shut- down, you may already have power through the bypass line. You can determine this by observing the Monitor/Mimic Display screen at the System Control Cabinet (SCC).

85

Page 91
Image 91
Emerson Series 610 manual