Operation

3.4.5Shutdown Procedures System Shutdown Procedure

Perform a System Shutdown Procedure when you want to remove power from the UPS system and System Control Cabinet (SCC) when required for maintenance or if you need to perform maintenance on a UPS module in a non-redundant system.

Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.0 - Maintenance.

Use the SCC Monitor/Mimic Display to determine the operating condition of the UPS system. From the SCC Master Menu, select the Shutdown Procedures screen.

Figure 67 SCC shutdown procedures screen

© 1989-2003

SHUTDOWN PROCEDURES

1.If load is not already being supplied by the bypass line, select the

"LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer the load to bypass.

2.Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES."

3.Press the ALARM RESET button to clear alarms which are no longer active.

4.If necessary for maintenance purposes, open the static switch disconnect circuit breakers.

5.Wait approximately two (2) minutes before attempting any other action .

Step 1. If the UPS system is supplying power to the load (Load On UPS), select the Load Transfer Procedures screen at the SCC and perform a manual transfer to the bypass line (Load On Bypass), see 3.4.3 - Load Transfer Procedures. This will open the motorized UPS Output circuit breaker (see Figure 9) and close the motorized System Bypass circuit breaker (SBB, Figure 9).

Step 2. If maintenance is required on the Static Bypass Switch, set the Static Switch Disconnects to OFF (open). Refer to Figure 9.

NOTE

Depending on SCC model, the static switch disconnects can be two circuit breakers, contactors or plug-in connections on a drawout carriage assembly. The location could be at the front, right or rear of the cabinet. Refer to the drawing of the SCC cabinet selected for your UPS system.

! CAUTION

The UPS bypass line is still energized.

Step 3. If maintenance is required in the area of the SCC controls or the motorized system circuit breakers (UPS Output and SBB), transfer the load to the Maintenance Bypass, if available (see 3.4.4 - Maintenance Bypass Load Transfers).

! CAUTION

If your installation does not include a Maintenance Bypass, power must still be isolated from both sides of the UPS circuit breakers if maintenance is required. This will result in loss of power to the critical load. Perform an orderly load shutdown before isolating power.

! WARNING

Lethal voltages are present within this unit even when it is not on or when utility is not being supplied. Observe all cautions and warnings in this manual. Failure to do so could result in serious injury or death. Do not work on or operate this equipment unless you are fully qualified to do so! Never work alone.

Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.0 - Maintenance.

93

Page 99
Image 99
Emerson Series 610 manual Shutdown Procedures System Shutdown Procedure, SCC shutdown procedures screen

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.