Figure 9 Operator controls, typical SCCT System Control Cabinet

Operation

Figure 9 Operator controls, typical SCCT System Control Cabinet

Table 2

Typical SCCT System Control Cabinet operator controls

 

 

 

 

Item

 

Description

Function

 

 

 

 

1

 

UPS Output Circuit

This motorized circuit breaker connects the critical load to the UPS system

 

Breaker

output.

 

 

2

 

System Bypass Circuit

This motorized circuit breaker connects the critical load to the bypass line.

 

Breaker

 

 

 

3

 

Operator Control Panel

Refer to Figure 10 for controls available on this panel.

 

 

 

 

4

 

Interlock Button

Refer to Figure 11.

 

(on rear of Control Panel)

 

 

 

5

 

Close Bypass Switch

Refer to Figure 11.

 

(behind door)

 

 

 

6

 

Bypass Reset Switch

Refer to Figure 11.

 

(behind door)

 

 

 

 

 

 

These manually operated switches disconnect the static switch from the

 

 

 

bypass line and from the critical load. They are normally ON (closed). Turn

 

 

Static Switch Disconnects

them OFF (open) only to isolate (disconnect) the static switch for

7

 

maintenance procedures. For SCCT less than 1600A, the static switch

 

(behind door)

 

 

disconnects are contactors that open automatically upon loss of bypass input

 

 

 

 

 

 

power and close automatically when bypass power is restored. Control power

 

 

 

fuse disconnects are used to manually open the contactors for maintenance.

 

 

 

Press these two switches before closing Static Switch Disconnects when

 

 

Reset Switches (SW1) for

recovering from a shutdown that includes loss of Control Power. Green LED

8

 

Static Switch Disconnects

on means Control Power is available. Red LED on means Reset Switch

 

 

(behind door)

needs to be pushed. Only SCCI and SCCC control cabinets and SCCT

 

 

 

1600A and larger.

9

 

Control Power Disconnect

Normally ON. Fuseblocks that are labeled F7 through F10. Turn OFF Control

 

(behind door)

Power only when required for maintenance procedures.

 

 