Emerson Series 610 manual Master Menu Screen, SCC and module master menu screens

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 32
Image 32
3.2.1Master Menu Screen

Operation

Figure 12 illustrates the primary screens that you can access through the Operator Interface Display System. The liquid crystal display (LCD) screen provides a full 80 characters by 25 lines of informa- tion for easy readability. The following sections describe what these screens display and how and when to use them.

Module status information is available on the display screen, provided Control Power is ON, even when the UPS module is not operating. System status information is available on the SCC display screen and at local and remote terminals when at least one module is on-line or when the bypass source is available.

The screen will automatically display the Monitor/Mimic during normal operation. The System con- figuration screen will be displayed during start-up and whenever a system reset is required.

If a module display screen is blank, either power is not available, the Rectifier Input (RIB) circuit breaker (external to the UPS module) is open or the Control Power switch is OFF. If power is avail- able and a display is blank, contact Liebert Global Services (1-800-LIEBERT). Note that status infor- mation may be available at local and remote terminals. Use control touch pads at the SCC to manually transfer the critical load to the bypass line if the SCC display goes blank while load is on UPS (a very unlikely event).

3.2.1Master Menu Screen

The Master Menu contains the primary menu selections that monitor and control the operation of the UPS.

Figure 13 SCC and module master menu screens

 

 

 

UP : CURSOR UP

 

 

 

 

 

 

 

DOWN : CURSOR DOWN

© 1989-2003

 

 

 

SELECT : CHOOSE

MASTER MENU

 

 

 

 

 

 

 

 

 

 

MONITOR/MIMIC DISPLAY

 

START-UP PROCEDURES

STATUS REPORTS

SHUTDOWN PROCEDURES

SYSTEM CONFIGURATION

METER CALIBRATION

LIMIT SETTINGS

BATTERY EQUALIZE

LOAD TRANSFER PROCEDURES

CUSTOMER ALARM DEFINITIONS

SCC Master Menu

 

 

 

UP : CURSOR UP

 

 

 

 

 

 

 

DOWN : CURSOR DOWN

© 1989-2003

 

 

 

SELECT : CHOOSE

MASTER MENU

 

 

 

 

 

 

 

 

 

 

MONITOR/MIMIC DISPLAY

 

START-UP PROCEDURES

WALK-IN DISPLAY

SHUTDOWN PROCEDURES

STATUS REPORTS

BATTERY TIME

SYSTEM CONFIGURATION

METER CALIBRATION

LIMIT SETTINGS

BATTERY EQUALIZE

Module Master Menu

26

Page 32
Image 32
Emerson Series 610 manual Master Menu Screen, SCC and module master menu screens