Operation

3.4.2UPS Module Start-Up

When a UPS module has been shut down for any reason, use this procedure to start-up the UPS mod- ule to provide filtered, reliable power to the critical bus. This procedure gives step-by-step instruc- tions for controls to operate and conditions to observe. Your present situation could be initial start-up or recovering from input power failure, battery shutdown, maintenance shutdown or an emergency shutdown.

Perform this module start-up procedure at each module in your UPS system until all required mod- ules are on-line.

Step 1. Before you apply power to the UPS module, determine the position of the following circuit breakers and switches:

a.Rectifier Input Breaker (RIB) - If this external circuit breaker is closed, you already have power to the UPS cabinet and possibly power to the controls. If this breaker is closed, leave it closed. If it is open, leave it open until you are ready to apply power to the UPS cabinet.

b.Input Circuit Breaker (CB1) - Verify that this breaker on the front of the UPS module cabinet (Figure 8) is in the OFF position.

c.Module Battery Disconnect (MBD) - Verify that this external breaker is open or tripped.

d.Module Output Circuit Breaker (CB2) - Verify that this breaker on the front of the UPS module cabinet (Figure 8) is in the OFF position.

e.Control Power - The fuses labeled Control Disconnect should be ON (pushed in) unless you are recovering from a maintenance shutdown. If control power is OFF (fuseholders pulled open), leave it OFF until you are ready to apply power to the UPS controls.

Power must be provided to the UPS module controls so you can use the LCD and so the system logic can perform its control functions. Note that you can use the LCD to monitor UPS status, even when the UPS module is not on-line. If the LCD is operating, you already have Control Power. This will be the usual condition, unless you are recovering from a maintenance shutdown.

Step 2. If the LCD is not operating, energize Control Power by operating the following two controls:

a.Close the Rectifier Input Breaker (RIB), which is outside the UPS cabinet. This will provide power to the UPS cabinet but not to any UPS components.

b.Open the UPS cabinet door and close the Control Disconnect fuseholders to turn the Control Power ON. See Figure 8. Close the UPS cabinet door.

NOTE

Wait 2 minutes after applying control power before operating any other UPS module controls.

Press the Select pad on the UPS module to put the Master Menu on the LCD. Move the highlighted cursor to Start-Up Procedures (use the Up and Down pads). Press the Select pad to display the Start-Up Procedures screen. Return to this screen whenever you need to see the start-up instructions.

Select the Monitor/Mimic Display on the LCD. In the ALARM MESSAGES block (see Figure 15), the only alarm present should be Battery CB Open. If any other alarm messages are present, do not pro- ceed with the module start-up. Contact Liebert Global Services (LGS) for assistance.

88

Page 94
Image 94
Emerson Series 610 manual UPS Module Start-Up

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.