Emerson Series 610 manual Load Transfer Procedures Screen, Load transfer procedures screen

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 60
Image 60
3.2.8Load Transfer Procedures Screen

Operation

3.2.8Load Transfer Procedures Screen

Go to the SCC Master Menu and move the highlighted cursor to LOAD TRANSFER PROCE- DURES. Note that this screen is displayed at the System Control Cabinet but is not required at the UPS modules. Press the Select pad and the Load Transfer Procedures screen is displayed.

The Load Transfer Procedures screen contains instructions to transfer the critical load between the UPS system and the bypass line. Comparisons of the UPS and bypass voltage, frequency and phase synchronization are displayed along with transfer status messages and an indication of circuit breaker overlap time. The metered parameter values on the Load Transfer Procedures screen are updated at half-second intervals.

Refer to 3.4.3 - Load Transfer Procedures for more details.

Figure 41 Load transfer procedures screen

HISTORY

 

 

 

 

MODULE1 -0-0 04/10/97/17/98 16:49:2111:21:59 FRAME36100

 

 

 

 

SELECT : MASTER MENU

- 00000

 

SITE TAG - 00000002

 

 

 

 

 

 

 

 

 

 

VOLTAGE COMPARISON

 

 

Low Batt Warning

SYNCHRONIZATION

 

**** ACTIVE ALARMS ****

BattOutputDischargingOv-volts

 

 

 

 

 

 

 

UPS

-

A-B B-C C-A

B

FREQUENCY

-30

 

0

 

+30

 

480

480

A480

 

C

DC

LOAD

 

HERTZ

TIME

 

 

 

 

 

OUTPUT VOLTS

480

380

 

380

38060.0 Hz

 

 

 

 

 

 

 

 

 

 

BYPASS

-

481

479

4

53041 60.0 Hz

 

 

 

 

 

 

 

 

 

 

OUTPUT AMPS

 

53041

 

41530

 

 

 

 

 

 

 

 

 

 

OUTPUT FREQUENCY

3

 

 

MANUAL

 

 

50.0

 

 

 

 

 

 

OUTPUTLOAD KVAVOLTS

 

 

 

380

380

 

349

 

UPS LEAD

=

2 Deg

 

 

 

 

ON UPS

 

 

 

TRANSFER INSTRUCTIONS

 

 

 

 

 

 

 

 

 

OUTPUTBYPASS VOLTSAMPS

 

38041

 

41380

41380

 

 

 

 

 

 

 

 

 

 

 

OK TO TRANSFER

 

1.

Adjust the UPS voltage (1 - 5 volts) above the

 

 

 

 

 

OUTPUTTRANSFERVOLTSPROHIBIT

380

 

bypass voltage using the VOLTAGE ADJUST pot.

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

OUPUT AMPS

 

 

2.

If the OK TO TRANSFER message is highlighted,

 

 

 

 

 

 

 

410

 

410

410

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

simultaneously press the BYPASS and CONTROL ENABLE

 

BATTERY AMPS

 

0

 

buttons.

0

-583

 

 

 

 

 

 

 

 

 

 

INPUT VOLTS

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

INPUT AMPS

 

 

3.

Verify that the transfer was

successful by checking the

 

 

 

 

 

 

0

 

0

 

0

 

 

 

UP :

NEXT FRAME

 

 

 

 

 

 

 

 

 

 

380

 

breaker status on the "MONITOR/MIMIC" screen.

 

 

 

 

 

OUPUT VOLTS

 

 

 

380

380

 

 

 

 

 

 

 

 

 

 

 

OUTPUT AMPS

 

4.

Press the ALARM RESET button to clear alarms which

 

 

 

 

 

410

 

410

410

 

 

 

DOWN :

PREVIOUS FRAME

 

LOAD KVA

 

 

 

 

are no longer active

270

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT : EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item 1 - Voltage Comparisons: This chart shows the UPS and bypass voltage and frequency com- parisons between each of the three phases. If the UPS and bypass voltages are not within specified tolerances, a manual transfer is not permitted and TRANSFER PROHIBIT is highlighted.

The Voltage Adjust knob (push-to-turn), located on the SCC Operator Control Panel (Figure 10), is used to adjust the UPS output voltage (1 - 5 volts) above the bypass voltage. When the UPS and bypass voltages are within the specific tolerance, a manual transfer is possible and OK TO TRANS- FER is highlighted.

! CAUTION

The UPS output voltage responds very slowly to inputs from the Voltage Adjust knob. Make small adjustments and wait several seconds each time for voltage to stabilize before continuing.

Item 2 - Synchronization: This display shows the phase synchronization between the UPS output and bypass power. If the phase displacement is outside of the tolerance, a manual transfer is not per- mitted and TRANSFER PROHIBIT is highlighted.

During normal operation, the synchronization display should read UPS LEAD from zero to 4 degrees.

Item 3 - Status Messages: Three messages are constantly displayed here. Only the active message is highlighted. If TRANSFER PROHIBIT is highlighted, manual transfers/retransfers cannot be performed and automatic retransfers will not be initiated.

Item 4 - Manual Transfer Instructions: These instructions assist the operator in transferring the critical load between the UPS system and the bypass line.

If the load is on the bypass line, step 2 on the screen will instruct you to press the UPS and Control Enable buttons to retransfer the load from the bypass line to the UPS system.

54

Page 60
Image 60
Emerson Series 610 manual Load Transfer Procedures Screen, Load transfer procedures screen