Emerson Series 610 manual History Status, History status report screens

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 46
Image 46
History Status

Operation

History Status

The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen. Note that the values for output volts and amps are updated once each millisecond. Alarms are listed in the sequence they occurred, within 1 millisecond resolution. The frames are stored in a buffer (a computer information storage technique). The buffer stores the frames in a first in, first out sequence. As a new frame enters the buffer the oldest one is released.

When a designated fault occurs (see list below), the buffer stores information for the next 24 frames and then freezes (stops gathering information). At that time, the History Status screen contains

40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This

64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up and Down pads to view the screens.

Figure 25 History status report screens

 

HISTORY STATUS

 

MODULE-0 04/10/97

16:49:21

FRAME 36

 

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS ****

Output Ov-volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

DC

 

LOAD

HERTZ TIME

OUTPUT VOLTS

 

480

480

480

 

 

 

 

 

 

 

 

 

OUTPUT AMPS

 

420

420

420

 

 

 

 

 

 

 

 

 

OUTPUT FREQUENCY

 

 

 

 

349

60.0

 

 

 

 

LOAD KVA

 

480

480

480

 

 

 

 

 

 

BYPASS VOLTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP

: NEXT FRAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN : PREVIOUS FRAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT : EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HISTORYSTATUS

MODULE-0-0 04/10/97/17/98

16:49:2111:21:59

FRAME36100

ORDER - 000000 SITE ID - 00000

SITE TAG - 0000000

 

 

 

 

 

**** ACTIVE ALARMS ****

BattOutputDischargingOv-volts

Low Batt Warning

 

 

 

 

 

 

 

 

 

A

B

C

DC

LOAD

HERTZ

TIME

OUTPUT VOLTS

4380

4380

4380

 

 

 

 

 

 

 

 

 

 

OUTPUT AMPS

325530

325530

325530

 

 

 

 

 

 

 

 

 

 

OUTPUT FREQUENCY

 

 

 

 

 

 

 

650.0

 

 

 

 

OUTPUTLOAD KVAVOLTS

480

480

480

 

349

 

 

 

 

 

 

OUTPUTBYPASS VOLTSAMPS

32580

32580

32580

390

 

 

 

 

 

 

 

 

 

BATTERY VOLTS

 

 

 

 

 

 

 

 

0:01

 

 

 

OUTPUT VOLTS

480

480

480

 

 

 

 

 

 

 

 

 

 

OUPUT AMPS

325

325

325

-645

 

 

 

 

 

 

 

 

 

BATTERY AMPS

 

 

 

 

 

 

 

 

 

 

 

 

INPUT VOLTS

0

0

0

 

 

 

 

 

 

 

 

 

 

INPUT AMPS

0

0

0

 

 

 

 

UP : NEXT FRAME

OUPUT VOLTS

480

480

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN : PREVIOUS FRAME

OUTPUT AMPS

325

325

325

 

 

 

 

LOAD KVA

 

 

 

 

270

 

 

 

 

 

 

 

SELECT : EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Page 46