Emerson Series 610 manual Alarm messages - meaning and corrective action continued, Operation

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 73
Image 73
Refer to 3.2.14 - Alarm and Status Messages.

Operation

Table 9

Alarm messages - meaning and corrective action (continued)

Alarm

 

 

Cabinet

Special

 

Message

 

Location

Functions

Meaning and Corrective Action

UPS SYSTEM (Cont’d.)

 

 

 

 

 

 

 

The load on the UPS has exceeded the current versus time window of

Overload

 

 

SCC

D, F, L, S

system overload capacity. The UPS system transfers the load to bypass.

 

 

Reduce the load. If the system does not initiate an automatic load

Transfer

 

 

 

 

 

 

retransfer, manually retransfer the critical load from the bypass line to the

 

 

 

 

 

 

 

 

 

 

UPS. Reset the alarm.

 

 

 

SCC

S

An alarm message (see lists in SCC and module remote monitor

Module Summary

 

 

indications and Other alarms that activate summary alarms in 3.2.6 -

 

 

 

 

System Configuration Screens) or the watchdog timer has activated the

Alarm

 

 

MMU

R

 

 

Module Summary Alarm.

 

 

 

 

 

 

 

 

 

 

Clear alarm conditions, if possible.

Module N Off

 

SCC

D

The output circuit breaker of Module N is open. The number N will identify

 

 

 

the module (1 through 6).

 

 

 

Line

 

 

MMU

R

 

 

Review active alarms at Module N and clear alarm conditions, if possible.

 

 

 

 

 

 

 

 

 

 

Inverter output is not synchronized with the UPS system critical bus. This

Inverter

 

 

 

 

also means the output circuit breaker is open and should not be closed

 

 

MMU

until the output is in sync. This condition may correct itself. If not, shut

Nonsynchronized

 

 

down the UPS module and then perform a start-up procedure.

 

 

 

 

 

 

 

 

 

 

Contact Liebert Global Services if condition persists.

 

 

 

 

 

The UPS output current has exceeded 175% of the rated full load or the

Overload

 

 

 

 

overload capacity has been exceeded. The UPS module is taken off-line

 

 

MMU

D, F, L, S

and shut down.

Shutdown

 

 

 

 

 

 

Contact Liebert Global Services at once. Do not attempt to reset circuit

 

 

 

 

 

 

 

 

 

 

breakers.

 

 

 

 

 

Excessive reverse power flow from the critical bus into the UPS inverter

 

 

 

 

 

has occurred, probably because of low inverter output voltage or a phase

Reverse Power

 

MMU

D, F, L, S

mismatch. The UPS module is taken off-line and is shut down.

 

 

 

 

 

Contact Liebert Global Services immediately. Do not attempt to reset

 

 

 

 

 

circuit breakers.

 

 

 

 

 

At least one of the fuses has opened or a rectifier fault was detected. UPS

Rectifier Fuse

 

MMU

D, F, S

module is taken off-line and is shut down.

Blown

 

 

Contact Liebert Global Services immediately. Do not attempt to reset

 

 

 

 

 

 

 

 

 

circuit breakers.

 

 

 

 

 

At least one of the fuses has opened or an inverter fault was detected.

Inverter Fault

 

MMU

D, F, S

The UPS module is taken off-line and is shut down.

 

Contact Liebert Global Services immediately. Do not attempt to reset the

 

 

 

 

 

 

 

 

 

 

circuit breakers.

Communication

 

SCC

S

The COM FAIL status message is as important as an alarm message.

Failure

 

 

Refer to 3.2.14 - Alarm and Status Messages.

 

 

 

 

 

 

 

 

 

The optional Battery Cycle Monitor can retain information about the last

Battery Cycle

 

 

 

132 battery discharge events. When the storage buffer approaches its

 

MMU

D, S

capacity, this warning message is broadcast via terminal and modem

Buffer Warning

 

 

 

 

communication channels and a complete listing of all records is sent to

 

 

 

 

 

 

 

 

 

 

the terminal port. The message clears after 30 seconds.

 

 

 

 

 

Battery self-test can be enabled from System Options screen. For test to

 

 

 

 

 

start, the following conditions must be valid:

 

 

 

 

 

1. No Battery Overtemp Alarm must exist.

 

 

 

 

 

2. Battery input and output circuit breakers must be closed.

Battery Exercise

 

MMU

3. All three input volt phases must be within nominal range (+10%, -20%).

 

4. DC volts must be greater than (DC Ref) -20V. For a 540 bus, the

 

 

 

 

 

 

 

 

 

 

nominal float voltage for 240 cells (the DC voltage reference setting) the

 

 

 

 

 

DC voltage on the battery must be greater than 520VDC.

 

 

 

 

 

5. Battery charge must be greater than 90%.

 

 

 

 

 

6. Load must be greater than 15%.

Table 9 Abbreviations

 

 

 

D = auto-dial;

 

L = latches

 

 

E = logs only;

 

R = remote

 

 

F = freezes;

 

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

67

Page 73
Image 73
Emerson Series 610 manual Alarm messages - meaning and corrective action continued, Operation