Emerson Series 610 manual Alarm messages - meaning and corrective action, Operation

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 71
Image 71
Alarm messages - meaning and corrective action

Operation

Table 9

Alarm messages - meaning and corrective action

Alarm

 

 

Cabinet

Special

 

Message

 

Location

Functions

Meaning and Corrective Action

AC INPUT

 

 

 

 

 

 

 

 

 

 

The rectifier input line voltage is outside of specified limits or the input

 

 

 

 

 

circuit breaker is opened while the battery circuit breaker remains closed.

Input Fail

 

 

MMU

The battery supplies power to the critical load through the UPS inverter.

 

 

 

 

 

Provide an alternate source of AC power or prepare to initiate critical load

 

 

 

 

 

procedures when battery reserve time is low.

DC BUS

 

 

 

 

 

 

 

 

 

 

Either the positive (+) or negative (-) DC bus is grounded. No transfer or

DC Ground Fault

 

MMU

D, L, S

shutdown occurs.

 

Contact Liebert Global Services at once. Do not attempt to locate or repair

 

 

 

 

 

 

 

 

 

 

the fault.

 

 

 

 

 

At least one DC capacitor fuse has opened. The UPS module is taken off-

DC Capacitor

 

MMU

D, F, S

line and the input and battery circuit breakers trip open.

Fuse Blown

 

 

Contact Liebert Global Services at once. Do not attempt to reset the

 

 

 

 

 

 

 

 

 

circuit breakers.

 

 

 

 

 

The module battery circuit breaker (MBD) is open. This circuit breaker can

 

 

 

 

 

be opened either manually or automatically in a UPS shutdown

 

 

 

 

 

procedure. If the UPS is operating with this breaker open, the critical

Battery CB Open

 

MMU

D, R, S

load is not protected from loss of the utility source power.

 

 

 

 

 

After AC power is restored and the DC bus is at 100% operating voltage,

 

 

 

 

 

manually close the battery circuit breaker so the rectifier can charge the

 

 

 

 

 

battery.

 

 

 

 

 

The battery is discharging. This occurs whenever the battery supplies

 

 

 

 

 

power to the load for more than 5 seconds because of input power failure,

 

 

 

 

 

a rectifier problem or an overload condition. If the input power or a source

Battery

 

 

MMU

D, R, S

of auxiliary power is restored to the UPS module, the UPS automatically

Discharging

 

 

returns to normal operation.

 

 

 

 

 

 

 

 

 

Watch the battery voltage carefully. Reduce the load (begin controlled

 

 

 

 

 

shutdown) to extend the battery back-up time. Reset the UPS alarms after

 

 

 

 

 

the input power is restored. The message clears after 30 seconds.

 

 

 

 

 

The battery voltage is approaching the minimum discharge voltage

Low Battery

 

 

MMU

D, R, S

(approximately 5 minutes remaining).

Warning

 

 

Complete the controlled shutdown of the critical load. Reset the alarms if

 

 

 

 

 

 

 

 

 

the input power is restored before shutdown.

 

 

 

 

 

The battery voltage has decreased to the minimum discharge value. The

Low Battery

 

 

 

 

UPS module is taken off-line (no power to the critical load) and the

 

 

MMU

D, F, L, S

battery and input circuit breakers trip open.

Shutdown

 

 

 

 

 

 

Perform a UPS system start-up procedure when AC power becomes

 

 

 

 

 

 

 

 

 

 

available.

 

 

 

 

 

The maximum preset value of the DC Bus voltage has been exceeded.

DC Overvoltage

 

 

 

The UPS module is taken off-line and the input and battery circuit

 

MMU

D, F, L, S

breakers trip open.

Shutdown

 

 

 

 

 

 

Contact Liebert Global Services at once. A fault may have occurred within

 

 

 

 

 

 

 

 

 

 

the UPS. Do not attempt to reset the circuit breaker.

BYPASS

 

 

 

 

 

 

 

 

 

 

The critical load is being supplied power from the bypass line and is

Load On Bypass

 

SCC

D

therefore exposed to utility power disturbances.

 

Clear all of the alarms before attempting to retransfer the load from the

 

 

 

 

 

 

 

 

 

 

bypass line to the UPS.

Table 9 Abbreviations

 

 

D = auto-dial;

 

L = latches

 

 

E = logs only;

 

R = remote

 

 

F = freezes;

 

S = summary

 

 

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs

D# = auto-dial initiated through Module N (1-6) off-line

65

Page 71
Image 71
Emerson Series 610 manual Alarm messages - meaning and corrective action, Operation