Emerson Series 610 Load Block Messages, Alarm Messages, Abbreviations used in alarm messages

Models: Series 610

1 120
Download 120 pages 16.72 Kb
Page 70
Image 70
Load Block Messages

Operation

Load Block Messages

Status messages in the Load Block indicate how many modules are in the system, how many modules are ON LINE and whether the system is operating in the redundant mode.

The following status messages may appear in the load block.

1.N OF X MODULES CONNECTED: The number N is the number of UPS modules ON LINE. This means the module output circuit breaker is closed. X is the number of UPS modules in the system (connected to this SCC). This number is set from the System Configuration screen.

2.REDUNDANT: The capacity of the UPS modules ON LINE is sufficient to supply the critical load even if one module is taken OFF LINE. The critical load will remain on the UPS system if one module goes OFF LINE.

3.NON-REDUNDANT:The critical load will be transferred to bypass if one module goes OFF LINE and you must transfer the load to bypass in order to perform maintenance on any UPS module.

4.TIME TO OVERLOAD TRANSFER: During an overload condition, the time remaining before transfer (in seconds) is displayed at the bottom of the load block. At each Module (MMU), the message is Time to Overload Shutdown.

Alarm Messages

The alarm message area displays the alarm conditions that are present within the UPS system. Alarm messages are displayed in flashing reverse video. During normal operation no alarm messages should be present. Up to four messages are displayed. To see if any additional alarm conditions are present in the UPS system, display the Present Status screen on the control panel.

Table 9 is a complete list of all alarm messages and corrective actions, if any. The first column lists the alarm message, with related alarms grouped together.

The third column indicates which special functions (if any) are initiated by the alarm.

D - The alarm initiates an auto-dialcall through a user-provided modem to a remote terminal. E - Message displayed only on Status Report screens including Event History.

F - The alarm freezes the History Status Report memory buffer in the cabinet where the alarm is displayed. Pressing the Alarm Reset pad for more than 5 seconds will unfreeze the memory buffer as long as the alarm is no longer active.

L - The alarm latches the displayed alarm message. Some alarm conditions are temporary (tran- sient) and may not last long enough to be noticed. Latching the display (keeping it on) lets you know that an alarm condition has occurred. A latching display alarm remains on the display screen until the alarm condition is removed and the Alarm Reset pad is pressed.

R - The alarm is displayed on an (optional) Remote Monitor Panel. This information is also avail- able for customer use through a set of contacts on a separate terminal board.

S - The alarm initiates a summary alarm at the Remote Monitor Panel and at the SCC.

The fourth column provides an explanation of the alarm condition, the critical bus status and the corrective actions, if any, to remedy the alarm.

Table 8 Abbreviations used in alarm messages

Abbreviation

Definition

Auto

Automatic

Avail

Available

Batt

Battery

Byp

Bypass

 

 

Cap Fuse

Capacitor Fuse

Cont Power

Control Power

Equip

Equipment

 

 

H/W

Hardware

Inv Fuse

Inverter Fuse

OF/UF

Over/Under Frequency

 

 

Abbreviation

Definition

Ov-temp

Overtemperature

O-volt

Overvoltage

O-volts

Overvoltage

Ph Seq

Phase Sequence

 

 

Rect Fuse

Rectifier Fuse

Rexfer

Retransfer

Shutdn

Shutdown

 

 

Static Sw

Static Switch

Un-volts

undervoltage

Xfer

Transfer

 

 