Menu Configuration
51 LRP2000 Passive Reader/Writer
If option 2 or 3 is selected from the “Power Up In Continuous Read Mode” menu, the following prompts
appear to allow you to specify the starting tag address, how many bytes will be read, the Family Code
subset of tags to be read, the number of different tags that must be seen before the same tag will be read
again, and what the Raw Read Response should be:
Start Address (0 to 111)
Length (1 to 112)
Family Code
Tag Delay (0 to 225)
Raw Read Response? [0] NO [1] CR terminate [2] CR/LF terminate
Power up in Continuous Read Mode?
You also have the option of setting the LRP2000 to start up in Continuous Read Mode. When you have
configured the LRP2000 to function in this manner, you do not issue commands to the LRP2000. It will,
upon start up, enter directly into a Continuous Read Mode. Since this bypasses the normal command
parameters, you must specify the Continuous Read Mode parameters.
The LRP2000 responds to other commands and resumes Continuous Read Mode when completed.
If you are using your LRP2000 in this mode, you must choose whether you want the LRP2000 to read a
single tag or multiple tags within the field.
To exit Continuous Read Mode, you must either re-enter the Configuration Menu and select NO from the
Power up in Continuous Read Mode option, or issue a Continuous Read command from the host with a
length of 0 as described in Chapter 6, RFID Interface.
Start Address (0-XXX)
Enter the tag address where you want the read to begin.
Length (1-XXX)
Enter the length of the read you wish the LRP2000 to perform. Make certain that the leng th value does not
exceed the number of possible addresses following the starting tag address. Entering a read length of 0
disables Continuous Read Mode.
Delay Between Identical Decodes (0-60)
The Delay Between Identical Decodes parameters can have a value of 0 to 60 seconds. When the Delay
Between Identical Decodes is set to 0, the LRP2000 continuously reads AND transmits tag data to the
host. This can flood the buffers and cause communication errors and data loss.
Raw Read Response?
If you have selected ABx Fast or ABx ASCII, you have the option of stripping the command protocol from
the data and adding a terminator to separate the data packets. You can choose a CR (0DH) or CR/LF
(0DH, 0AH) to terminate the data.