20 | Installation (for qualified installers only) |
Vent Clearances
Vertical Penetrations
(through ceilings, roofs, etc.)
(firestop is required - sku 98900029)
1" Clearance To the Side
IN THE ENCLOSURE (under 78") Vertical or Horizontal Sections:
6" Clearance Above
2" Clearance Below
ABOVE THE ENCLOSURE (over 78")
Vertical Sections:
1" Clearance To the Side
Horizontal Sections:
4" Clearance Above
2" Clearance To The Side 2" Clearance Below
Horizontal Penetrations (through walls, etc.)
(thimble is required - sku 98900030) 4" Clearance Above
2" Clearance To The Side 2" Clearance Below
Vent Location
The starter section is set at a 45° angle. Place a 45° elbow directly on top of the fireplace and route it vertically or horizontally. The approximate position of the vent is shown below.
REAR VENT | TOP VENT |
1" |
46"
Framing to the rear of the fireplace.
NOTE: In cases where the vent is routed vertically directly above the fireplace, you may place a 90° elbow directly on top of the fireplace, followed by a 45° elbow that directs the vent upwards. For vent configuration purposes this is considered a top vent and the 90° and 45° elbow is considered a single 45° elbow.
Framing to the rear of the fireplace.
56"
© Travis Industries | 4090102 |