34

Installation (for qualified installers only)

Non-Combustible Facing

Non-combustible facing on the front of the fireplace must extend a minimum 16-1/2” from the top of the glass frame (49-1/2” from the base of the fireplace). Above 16-1/2” combustible facing may be used (see “Mantel Requirements” on the following page for more details).

Non-combustible facing on the front of the fireplace must extend a minimum 2” to each side of the glass frame. Beyond 2” combustible facing may be used, but may not protrude more than 4” (see “Mantel Requirements” on the following page for more details).

The maximum depth for non-combustible facing is 6” (includes the fiber board)

Combustible Material

(drywall, etc.

Fiber Board (required)

16-1/2”” Min.

Non-Combustible Facing (tile, rock, marble, etc.)

Fireplace

Glass Frame

Figure 23

© Travis Industries

4090102

100-01212_000

Page 34
Image 34
FireplaceXtrordinair 36CF installation manual Non-Combustible Facing