24
FVR-C9S-2UX

Function Code Tables

Function
Code Function Date Code Range Unit Min.
Set.
Factory
Setting
Change
During
Operation
F00 Data protection 0: Data change possible
1: Data change not possible —— 0 No
F01 Frequency
Command 0: Keypad panel (UP/DOWN keys)
1: Analog input (VR, DC0 - 10V or DC4 - 20mA) —— 1 No
F02 Operation
Command 0: Keypad panel operation (RUN/STOP keys)
1: External signal operation (FWD/REV terminals) —— 0 No
F03 Maximum
Frequency 50 - 120 Hz Hz 1 60 Hz No
F04 Base Frequency 50 - 120 Hz Hz 1 60 Hz No
F05 Acceleration TIme 0.0 - 60s (0.0 setting = 0.01s) s 0.1 6.0s Yes
F06 Deceleration Time 0.0 - 60s (0.0 setting = 0.01s) s 0.1 6.0s Yes
F07 Torque Boost 0 - 31 (code) 13 Yes
F08 Electronic Thermal
Overload Relay
Operation
0: Inactive
1: Active (standard 4-pole motor)
2: Active (forced-air cooled motor) —— 0 No
F09 Electronic Thermal
Overload Relay
Level 30 - 105% of rated current of drive % 1 100% No
F10 Restart after
Momentary Power
Failure
0: Inactive
1: Active (Restart drive in 0.5s after power failure) —— 0 No
F11 Gain for Frequency
Setting Signal 0: For 0 - 10 V
1: For 0 - 5 V —— 0 No
F12 DC Brake (Level
Setting) 0 - 100% 1 50% Yes
F13 DC Brake (Time) 0.0 (inactive) 0.1 - 30s s 0.1 0.1s Yes
F14 Starting Frequency 1 - 6 Hz Hz 1 1 Hz No
C92-01