1. Type

Drive Series

FVR-C9S-2UX

3. Warning and Caution

F V R F 2 5 C 9 S 2 U X

Power Series: 230V UX Series Applicable motor output (Hp)

2.Phase: 3PH - three-phase

3.Voltage range: 200V - 230V - AC200V Series

4.Frequency: 50/60Hz

5.Rated output capacity

6.Rated output current

7.Output frequency range: 1- 120 Hz

8.Serial No.

2. Part Names

4

2

PRG

RUN

RESET

 

FUNC

STOP

DATA

 

FVR-C9S

3

1

CLOSED OPEN

4

5

Improper wiring will result in damage to, and failure of the unit. Please carefully note the items listed below, and use the unit as indi- cated.

WARNING AND CAUTION

1.Do not impress power supply voltage that exceeds the standard specification volt- age permissible fluctuation. (Permissible voltage: AC200V - 230V)

2.Do not connect power supply to the drive output terminals (U, V, W). Connect power supply only to the power terminals (L1, L2 and L3)

3.Whenever removing the drive cover, al- ways switch off the power supply. Do not switch on the power supply to the drive with the drive cover removed.

4.Do not touch the live part until the CRG lamp located above the main circuit termi- nals goes out.

5.Avoid using a magnetic contactor (ON/ OFF) installed in the line side of the drive for RUN and STOP. Use the FWD-CM (forward) and REV-CM (reverse) terminals for RUN and STOP.

6.Do not connect a power factor correcting capacitor to the output side of the drive.

7.Do not perform a megger test between the drive terminals or on the control circuit terminals.

1.Drive Cover

2.Keypad Panel

3.Frequency Setting VR

4.Mounting Screw Holes

5.Drive Cover Screw

7

Page 7
Image 7
GE FVR-C9S-2UX Drive Series instruction manual Part Names, Type