FVR-C9S-2UX

UL/CSA

WARNING / AVERTISSEMENT

Hazard of electrical shock. Disconnect incoming power before working on this control.

Risque de choc electrique. Couper l’alimentation avant le depannage de sette commande.

More than one live circuit. See diagram. Cet equipment renferme plusieurs circuits sous tension. Voir le schema

CAUTION ATTENTION

Dangerous voltage exists until charge light is off. Prede tensions dangereuses tant que le voyant n’est pas eteint.

Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes. 240V maximum.

Use 60/75° C copper wire only.

Use Class 1 wire only.

Open type equipment

Tightening torque and wire range for field

Ê Ê Ê wiring terminals are as follows:

Model

Required

Wire

 

torque (N.m)

range

FVRF12C9S-2UX

0.98

14

FVRF25C9S-2UX

0.98

14

FVRF50C9S-2UX

0.98

14

FVR001C9S-2UX

0.98

14

FVR002C9S-2UX

0.98

14

FVR003C9S-2UX

0.98

14

FVR005C9S-2UX

1.777

12

Control board

 

 

terminal

0.7

24

Use the listed quick-acting fuse in series. Fac- tory recommendation is a Bussman type, JKS or equivalent. Fuses are required to validate the UL and CSA listings.

Model

Dist. fuse size,600V

FVRF12C9S-2UX5

FVRF25C9S-2UX5

FVRF50C9S-2UX5

FVR001C9S-2UX10

FVR002C9S-2UX20

FVR003C9S-2UX20

FVR005C9S-2UX30

Field wiring connection shall be made by a UL listed and CSA Certified closed-loop terminal connector sized for the wire gauge involved.

Connector must be fixed using the crimp tool specified by the connector manufacturer.

OTHER

WARNING:

FIRE AND PERSONAL INJURY HAZARD

Do not carry out any modifications to the drive. Doing so may result in electric shock and injury.

GENERAL CAUTION

All of the illustrations in this instruction manual show the drive with the covers and other protec- tive equipment removed in order to facilitate explanation of detailed parts of the drive. Be absolutely sure to return all covers and protective equipment to the prescribed positions before operating the drive, and make sure that all opera- tions are carried out in accordance with the instructions in this manual.

1. Inspection Upon Receipt

Please inspect the following items upon receipt of your drive.

Check the name plate to insure the specifi- cations correspond to those ordered.

Inspect the unit for damage which may have occurred during shipping.

If you have any problems or questions re- garding the drive, please contact the nearest Fuji sales office or the distributor where the unit was purchased.

Nameplate

 

 

 

 

 

 

 

 

 

 

1

TYPE

 

 

 

 

 

 

 

 

 

 

 

 

FVRF 12C9S-2UX

 

 

 

 

 

 

 

 

 

 

 

 

SOURCE

 

 

 

 

 

 

 

 

2 3 4

 

 

3PH 200-230V 0.9A 50/60 HZ

 

 

 

 

 

OUTPUT

 

 

 

 

5 6 7

3PH 200-230 0.7A 1/8HP 1-120HZ

 

 

SER. NO.

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuji Electric Co. Inc. Japan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Page 6
Image 6