30
FVR-C9S-2UX
F 1 4 Starting Frequency
The starting frequency can be set in increments of 1 Hz within a range of 1 to 6 Hz. Note that stopping will
also occur at the frequency set by this function.
1 1 Hz
6 6 Hz
Set to 2 Hz when using a high speed motor.
F 1 5 Motor Running Sound
The sound of the motor operation can be changed by changing the carrier frequency.
0Select from among 5 levels in accordance with the usage conditions.
5
Data code
0 Low carrier frequency
5 High carrier frequency (low noise)
F 1 6 Fault Memory
The current and previous 3 fault events are stored in memory.
The data for each can be displayed by using the DOWN key.
The procedure for displaying the data is as follows:
The information for any new trip will be stored in the area for the "information for the latest trip" shown
above, each trip history will be removed downward and the "information for the third preceding trip"
will be erased.

Output

frequency

Starting

frequency

1

No. Procedure
Display
(ex) Remarks
1Display
F16 F16
2Press FUNC/DATA Key Press UP Key The information for the latest
trip will be displayed
F01
3Press DOWN Key Press UP Key The information for the first
preceding trip will be displayed
OH2
4Press DOWN Key Press UP Key The information for the second
preceding trip will be displayed
OC1
5Press DOWN Key Press UP Key
The information for the third
preceding trip will be displayed.
(in this example, there is no
history of a third preceding trip).
---
6
Press DOWN Key
End
C92-12