| Restart After Momentary Power Failure |
|
|
|
|
|
|
|
| |||||
F 1 0 |
|
|
|
|
|
|
|
| ||||||||
It is possible to select whether or not to restart operation when power supply is resumed after |
|
|
|
| ||||||||||||
momentary power failure. |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| 0 | Inactive | While stopped: |
| Stopped condition is maintained even after power supply |
|
| ||||||||
|
|
|
|
|
| has been restored. |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| While running: After power supply has been restored. LU is lit and an alarm | ||||||||||||
|
|
|
|
|
| is outputted. |
|
|
|
|
|
|
|
| ||
|
| 1 | Active | Operation is restarted in 0.5s after power supply has been restored. |
|
| ||||||||||
|
|
|
| (When drive is stopped, it is maintained in the stopped condition even after |
|
| ||||||||||
|
|
|
| power supply has been restored). |
|
|
|
|
|
|
|
| ||||
|
|
|
| This is valid only if power supply is restored while LU is lit. The length of |
|
| ||||||||||
|
|
|
| time that LU will remain lit after a power failure occurs is as follows. |
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Drive Model |
| F12 | F25 |
| F50 | 001 | 002 |
| 003 |
| 005 |
|
|
|
|
| Time(s) |
| 0.7 | 0.7 |
| 1.4 | 1.4 | 4.0 |
| 5.5 |
| 9.0 |
|
F 1 1 Gain for Frequency Setting Signal
Outputs a frequency which is a proportional ratio of the analog frequency setting. Selects an analog input signal level when F O 1 is _ _ 1.
0 Maximum frequency is outputted at 10V
1 Maximum frequency is outputted at 5V | setting | |
| When used together with the frequency setting bias, | |
| this frequency setting gain takes priority, and the | |
| bias applied to the frequency after the gain has | |
| Frequency | |
| been applied. | |
|
|
1
0
5V 10V Analog input
F 1 2 DC Brake
The current level of DC brake can be set.
Taking the rated current of the drive as 100%, this current level can be set in increments of 1%.
F 1 3 DC Brake (Braking Time)
The DC braking time can be set.
0.0Inactive
0.1- 30.0 Braking time can be set within a
range of 0.1 to 30s (in increments of 0.1s)
Output | Output |
|
frequency | voltage |
|
3 Hz |
|
|
| Time | 1 DC braking |
29