100%

 

 

 

 

 

FVR-C9S-2UX

 

 

 

 

 

 

 

 

 

 

Restart After Momentary Power Failure

 

 

 

 

 

 

 

 

F 1 0

 

 

 

 

 

 

 

 

It is possible to select whether or not to restart operation when power supply is resumed after

 

 

 

 

momentary power failure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Inactive

While stopped:

 

Stopped condition is maintained even after power supply

 

 

 

 

 

 

 

 

has been restored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

While running: After power supply has been restored. LU is lit and an alarm

 

 

 

 

 

 

is outputted.

 

 

 

 

 

 

 

 

 

 

1

Active

Operation is restarted in 0.5s after power supply has been restored.

 

 

 

 

 

 

(When drive is stopped, it is maintained in the stopped condition even after

 

 

 

 

 

 

power supply has been restored).

 

 

 

 

 

 

 

 

 

 

 

 

This is valid only if power supply is restored while LU is lit. The length of

 

 

 

 

 

 

time that LU will remain lit after a power failure occurs is as follows.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive Model

 

F12

F25

 

F50

001

002

 

003

 

005

 

 

 

 

 

Time(s)

 

0.7

0.7

 

1.4

1.4

4.0

 

5.5

 

9.0

 

F 1 1 Gain for Frequency Setting Signal

Outputs a frequency which is a proportional ratio of the analog frequency setting. Selects an analog input signal level when F O 1 is _ _ 1.

0 Maximum frequency is outputted at 10V

1 Maximum frequency is outputted at 5V

setting

 

When used together with the frequency setting bias,

 

this frequency setting gain takes priority, and the

 

bias applied to the frequency after the gain has

 

Frequency

 

been applied.

 

 

1

0

5V 10V Analog input

F 1 2 DC Brake

The current level of DC brake can be set.

Taking the rated current of the drive as 100%, this current level can be set in increments of 1%.

F 1 3 DC Brake (Braking Time)

The DC braking time can be set.

0.0Inactive

0.1- 30.0 Braking time can be set within a

range of 0.1 to 30s (in increments of 0.1s)

Output

Output

 

frequency

voltage

 

3 Hz

 

 

 

Time

1 DC braking

29

Page 29
Image 29
GE FVR-C9S-2UX Drive Series instruction manual Gain for Frequency Setting Signal, DC Brake Braking Time