FVR-C9S-2UX
Function Code Tables
Function
Code Function Date Code Range Unit Min.
Set.
Factory
Setting
Change
During
Operation
F15 Motor Running
Sound 0 - 5 (code) 5 Yes
F16 Fault Memory The current and previous 3 fault events are displayed
in order of occurrence —— — No
F17 Data Initialization 0: Inactive
1: Reset to the initial value (value set at factory) —— 0 No
F18 Retry 0: Inactive
1: Active (Retry times fixed at 5, Retry starts in
.05s after trip) —— 0 No
F19 Motor
Characteristics 0 - 10 4 Yes
F20 Jump Frequency
Range 0 - 10Hz Hz 1 3 Yes
F21 Jump Frequency 1 0 - 120Hz Hz 1 0 Yes
F22 Jump Frequency 2 0 - 120 Hz Hz 1 0 Yes
F23 Jump Frequency 3 0 - 120 Hz Hz 1 0 Yes
F24 High Limiter 0 - 100% % 1 100 Yes
F25 Low Limiter 0 - 100% % 1 0 Yes
F26 Bias Setting 0 - 100% % 1 0 Yes
F27 THR Terminal
Function 0: External alarm input
1: Multistep speed selection (X1) —— 0 No
F28 BX Terminal
Function 0: Motor coast-to-stop command input
1: Multistep speed selection (X2) —— 0 No
F29 Multistep Speed
Setting 1 0.0 - 120 Hz Hz 1* 10.0 Hz Yes
F30 Multistep Speed
Setting 2 0.0 - 120 Hz Hz 1* 20.0 Hz Yes
F31 Multistep Speed
Setting 3 0.0 - 120 Hz Hz 1* 30.0 Hz Yes
F32 Meter Adjustment 0 - 99 (Full scale DC 6.5 - 10.5V) — 1 85 Yes
F33 Meter Output
selection 0: Output frequency monitor
1: Output current monitor — 1 0 Yes
*1 Frequency can be set in increments of 0.1 Hz within a range of 0.0 to 99.9 Hz, and can be set in increments of 1 Hz