7 Vent Information and Diagrams

A. Approved Pipe

This appliance is approved for use with Hearth & Home Technologies DVP and SLP venting systems. Refer to Section 16.B for vent component information.

DO NOT mix pipe, fittings or joining methods from differ- ent manufacturers.

The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.

WARNING! Risk of Fire or Asphyxiation. This appli- ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.

B. Vent Table Key

The abbreviations listed in this vent table key are used in the vent diagrams.

Symbol

Description

 

 

V1

First section (closest to appliance) of vertical length

 

 

V2

Second section of vertical length

 

 

H1

First section (closest to appliance) of horizontal length

 

 

H2

Subsequent sections of horizontal length

 

 

C. Use of Elbows

Diagonal runs have both vertical and horizontal vent as- pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 7.1).

Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216

mm)horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).

Vertical

 

mm)

mm)

12

 

in.(216

 

.

 

 

in

 

 

(305

 

8-1/2

8-1/2 in.

 

(216 mm)

 

Horizontal

 

Figure 7.1

D. Measuring Standards

Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.

Pipe measurements are shown using the effective length of pipe (see Figure 7.2 and 7.3).

Measurements are made from the appliance outer wrap, not from the standoffs.

Horizontal terminations are measured to the outside mounting surface (flange of termination cap).

Vertical terminations are measured to bottom of termination cap.

Horizontal pipe installed level with no rise.

 

 

 

 

Effective Height/Length

 

 

 

 

Pipe

inches

mm

 

 

 

 

DVP4

4

102

 

 

 

 

 

 

 

 

DVP6

6

152

 

 

 

 

DVP12

12

305

Effective

 

 

 

DVP24

24

610

Height/

DVP36

36

914

Length

DVP48

48

1219

 

 

 

 

DVP6A

3 - 6

76 - 152

 

 

 

 

DVP12A

3 - 12

76 - 305

 

 

 

 

DVP12MI

3 - 12

76 - 305

 

 

 

 

 

 

 

 

DVP24MI

3 - 24

76 - 610

Figure 7.2 DVP Pipe Effective Length

 

 

 

 

Effective Height/Length

 

 

 

 

 

 

 

Pipe

inches

mm

 

 

 

 

SLP4

4

102

Effective

 

SLP6

6

152

Height/

 

SLP12

12

305

 

SLP24

24

610

Length

 

 

SLP36

36

914

 

 

 

 

 

 

 

 

SLP48

48

1219

 

 

 

 

SLP6A

2 - 6

51 - 152

 

 

 

 

 

 

 

SLP12A

2 - 12

51 - 305

Figure 7.3 SLP Pipe Effective Length

E. Vent Diagrams

General Rules:

When penetrating a combustible wall, a wall shield firestop must be installed.

When penetrating a combustible ceiling, a ceiling firestop must be installed.

Horizontal runs of vent do not require vertical rise; horizontal runs may be level.

26

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF2089-980 Rev. o • 6/12

 