D. Secure the Vent Sections
•Vertical runs of DVP pipe must be supported every 8 ft. (2.44 m) after the 25 ft. (7.62 m) maximum unsupported rise.
•Vertical runs of SLP pipe must be supported every 8 ft. (2.44 m).
•Horizontal sections must be supported every 5 ft. (1.52 m).
•Vent supports or plumbers strap (spaced 120º apart) may be used to support vent sections. See Figures 10.8 and 10.9.
•Wall shield firestops may be used to provide horizontal support vent sections.
•SLP ceiling firestops have tabs that may be used to provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation! Improper support may allow vent to sag and separate. Use vent run supports and connect vent sections per in- stallation instructions. DO NOT allow vent to sag below connection point to appliance.
120º
Figure 10.8 Securing Vertical Pipe Sections
120º
Figure 10.9 Securing Horizontal Pipe Sections
E. Disassemble Vent Sections
•Rotate either section (see Figure 10.10) so the seams on both pipe sections are aligned as shown in Figure 10.11.
•Pull carefully to separate the pieces of pipe.
Figure 10.10 Rotate Seams for Disassembly
Figure 10.11 Align and Disassemble Vent Sections
Heat & Glo • | 47 |