Top Vent - Vertical Termination - (continued)
Two Elbows
Note: A 6 in. (152 mm) section of straight flue must be attached to the heater before a 90° elbow.
USE SLP SERIES COMPONENTS ONLY
V2
| V1 | H1 Maximum | V2 | V1 + V2 Min. | ||
Elbow only | Not allowed | * | * | * | ||
6 in. | 152 mm | 2 ft. | 610 mm | * | * | * |
1 ft. | 305 mm | 4 ft. | 1.22 m | * | * | * |
2 ft. | 610 mm | 6 ft. | 1.83 m | * | * | * |
3 ft. | 914 mm | 8 ft. | 2.44 m | * | * | * |
4 ft. | 1.22 m | 12 ft. | 3.66 m | * | * | * |
5 ft. | 1.52 m | 16 ft. | 4.88 m | * | * | * |
V1 + V2 + H1 = 36 ft. (10.97 m) Maximum
*No specific restrictions on this value EXCEPT V1 + V2 cannot exceed 32 ft. (9.75 m)